What is the voltage rating for this protective module?
The protective module is rated for a voltage of up to 690 V AC.
Can this module be used for three-phase applications?
Yes, it is designed for three-phase applications with a 3-pole configuration.
What types of protection does this module offer?
It offers thermal-magnetic protection, including phase imbalance protection.
What is the motor power compatibility of this module?
The module is compatible with motor powers ranging from 0.37 kW at 220...240 V AC up to 1.5 kW at 600...690 V AC.
What is the breaking capacity of this module?
The breaking capacity is >= 130 kA at voltages ranging from 220...240 V AC to 600...690 V AC.
What is the thermal protection adjustment range?
The thermal protection adjustment range is 0.1...12 A minimum at -20...60 °C without derating and 0.16...18 A maximum at -20...70 °C with derating.
What standards does this module comply with?
It complies with IEC 60947-6-1 and IEC 60947-6-2 standards.
What is the magnetic tripping current specification?
The magnetic tripping current is set at 15 A +/- 20% in accordance with various IEC standards.
What is the weight of this protective module?
The module weighs approximately 0.25 kg.
What is the utilisation category for this module?
The utilisation category for this module is AC-43.