What type of device is this Siemens component?
This Siemens component is an RCBO, which stands for Residual Current Circuit Breaker with Overcurrent protection. It is designed to protect electrical circuits from both overcurrents, such as short circuits and overload, and residual currents that could lead to electric shock hazards.
Can you explain the tripping characteristics of this RCBO?
The RCBO has a C-type tripping characteristic, meaning it is suitable for commercial and industrial applications with moderate inrush currents. It is designed to withstand sudden high current loads without tripping unnecessarily.
What is the rated residual current for this device?
The rated residual current for this RCBO is 300 mA, which is the level of fault current at which the device will trip to protect the circuit.
What are the installation requirements for this RCBO?
The RCBO should be installed in a distribution board with an IP20 protection class when connected conductors are installed. It can be mounted in any position and requires a space of two modular width units in the distribution board.
What is the mechanical service life of this RCBO?
The mechanical service life of the RCBO is typically 10,000 switching cycles, indicating its durability and reliability over time.
What are the environmental operating conditions for this RCBO?
The RCBO can operate within an ambient temperature range of -25 °C to 55 °C and can be stored in temperatures ranging from -40 °C to 75 °C. It is designed to withstand up to 95% humidity without condensation.
Is this RCBO halogen-free and silicon-free?
Yes, the RCBO is both halogen-free and silicon-free, making it suitable for use in environments where these characteristics are required for safety or performance reasons.
What is the breaking capacity of this RCBO?
The breaking capacity of the RCBO is 10 kA according to EN 61009-1, with a rated residual switching capacity of 10 kA according to IEC 61009-1.
Does this RCBO include neutral conductor switching?
Yes, this RCBO includes neutral conductor switching, which means it can disconnect both the live and neutral conductors in the event of a fault, providing additional safety.
What is the supply voltage and operating current for this RCBO?
The supply voltage for this RCBO at AC is rated at 230/240 V, and the operating current at AC is rated at 6 A.