What type of device is this?
This is a motor protection circuit breaker designed to protect electric motors from overloads, short circuits, and phase failures.
Can this device be used in any mounting position?
Yes, the device can be mounted in any position, offering flexibility in installation.
What is the rated operational voltage of this device?
The rated operational voltage of the device is up to 690V.
What is the significance of the trip class for this device?
The trip class, CLASS 10, indicates the time in seconds within which the device will trip in the event of an overload. For CLASS 10, this would typically be within 10 seconds at 600% of the rated current.
Is there a ground fault detection feature in this device?
No, this device does not have a ground fault detection feature.
What is the short-circuit current breaking capacity of this device?
The device has different breaking capacities depending on the voltage: 100kA at 240V, 55kA at 400V, 10kA at 500V, and 4kA at 690V.
What type of terminals does this device have for the main current circuit?
The device is equipped with spring-loaded terminals for the main current circuit.
What is the mechanical service life of the main contacts?
The main contacts have a mechanical service life of typically 100,000 switching cycles.
What are the dimensions of this device?
The device measures 119mm in height, 45mm in width, and 97mm in depth.
How can I determine the correct conductor cross-sections for connection?
The device can connect solid or stranded conductors of 2x (1 ... 10 mm²), finely stranded with core end processing of 2x (1 ... 6 mm²), and finely stranded without core end processing of 2x (1 ... 6 mm²).