What is this contactor used for?
This power contactor is used to switch electrical loads in industrial control circuits. Typical applications include starting and stopping three-phase motors on pumps, fans, conveyors and other machinery.
What motor power can this contactor switch at 400 V?
The contactor has an AC-3 motor switching rating of 7.5 kW at 400 V, with a rated operational current of 17 A. Selection should also take account of the motor's rated current and switching duty.
What control voltage does the coil require?
The 3RT2025-1AK60 has an AC coil rated for 110 V at 50 Hz or 120 V at 60 Hz. The control supply must match the voltage and frequency specified for the coil.
How many main and auxiliary contacts are included?
There are three normally open main contacts for switching the power circuit, plus one normally open and one normally closed auxiliary contact. The auxiliary contacts can be used for functions such as status indication and control interlocking.
Which terminals connect to the power circuit and control coil?
The incoming power terminals are labelled 1/L1, 3/L2 and 5/L3, with outgoing terminals labelled 2/T1, 4/T2 and 6/T3. The coil connects to A1 and A2. The normally open auxiliary contact uses terminals 13–14, while the normally closed auxiliary contact uses 21–22.
What are the dimensions and frame size?
This is a size S0 contactor measuring 45 mm wide, 85 mm high and 97 mm deep. Allow additional space in the enclosure for wiring, accessories and the required installation clearances.
How is the contactor mounted?
The contactor supports screw mounting or snap-on mounting onto a standard 35 mm DIN rail. These options allow it to be fitted into industrial control panels using either mounting arrangement.
What type of electrical connections does it use?
Screw-type terminals are used for the main power circuit, auxiliary contacts and control coil. Conductor size and termination method should be selected to suit the terminal specifications and the circuit requirements.
What is the operating temperature range?
The specified ambient operating temperature range is −25 °C to +60 °C. The temperature inside the control enclosure should be considered when assessing the installation.
Can additional auxiliary contacts be fitted?
Yes. The 3RT2025-1AK60 supports the addition of compatible auxiliary switch blocks where more control contacts are needed. Check the accessory's compatibility and the space available before selecting a block.
Does the 690 V rating refer to the coil voltage?
No. The rated insulation voltage is 690 V; it is separate from the coil's control supply rating. The coil requires 110 V AC at 50 Hz or 120 V AC at 60 Hz, not 690 V.