What is the voltage type of the control feed?
The control feed voltage type for the Siemens 3RH1122-1AF00 is AC.
What is the control supply voltage frequency?
The control supply voltage frequency for the Siemens 3RH1122-1AF00 is 50 Hz at the rated value and 60 Hz at the second rated value.
What is the operating range factor control supply voltage rated value of the magnet coil?
For the Siemens 3RH1122-1AF00, the operating range factor control supply voltage rated value of the magnet coil is 0.8 to 1.1 at 50 Hz for AC and 0.85 to 1.1 at 60 Hz for AC.
Does this part have an auxiliary switch?
Yes, the Siemens 3RH1122-1AF00 does come with an auxiliary switch.
What is the number of NC contacts for auxiliary contacts?
The Siemens 3RH1122-1AF00 has 2 NC contacts for auxiliary contacts.
What is the number of NO contacts for auxiliary contacts?
The Siemens 3RH1122-1AF00 has 2 NO contacts for auxiliary contacts.
What is the insulation voltage with degree of pollution 3?
The insulation voltage with degree of pollution 3 for the Siemens 3RH1122-1AF00 is 690 V.
What is the ambient temperature during operation?
The ambient temperature during operation for the Siemens 3RH1122-1AF00 is -25 to +60 degrees Celsius.
What is the resistance against shock?
The Siemens 3RH1122-1AF00 has a resistance against shock of 10g / 5 ms and 5g / 10 ms.
What is the impulse voltage resistance?
The impulse voltage resistance for the Siemens 3RH1122-1AF00 is 6 kV.