What type of electrical component is this?
It is a motor circuit breaker designed for motor protection applications. GV4PB50N is part of the TeSys GV4 range and combines thermal-magnetic protection with multifunction circuit breaker capability.
What current rating does it have?
The rated current is 50 A, with a thermal protection adjustment range of 20 to 50 A.
How many poles does it have?
It is a 3-pole device, making it suitable for three-phase motor protection applications.
What is the rated operational voltage?
The rated operational voltage is up to 690 V AC at 50/60 Hz according to IEC 60947-2, and 600Y/347 V AC at 60 Hz according to UL 489.
What breaking capacity does it provide?
The breaking capacity depends on the operating voltage. It is rated at 50 kA Icu at 380/415 V AC and 440 V AC, 100 kA Icu at 220/240 V AC, and 25 kA Icu at 500 V AC under IEC 60947-2.
What protection functions are associated with this device?
It is intended for motor protection and includes functions associated with overload, short-circuit, phase loss, phase unbalance, locked rotor, long start and jam conditions.
What type of terminals does it use?
It uses EverLink BTR screw connectors. The top terminals accept rigid conductors from 1.5 to 70 mm² and flexible conductors from 1.5 to 50 mm², while the bottom terminals accept rigid conductors from 2.5 to 95 mm² and flexible conductors from 2.5 to 70 mm².
What are the main physical dimensions?
The unit measures approximately 171 mm high, 81 mm wide and 116 mm deep, with a net weight of around 1.45 kg.
What environmental ratings apply to this component?
It has an IP40 degree of protection, IK07 impact rating and pollution degree 3. The operating temperature range is -25 to 70 °C, with storage from -50 to 85 °C.
What standards and certifications are listed for it?
The device is listed with standards including EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60947-4-1, UL 489 and CSA C22.2 No. 5. Product certifications include IEC, UL and CSA.
Can it be mounted in different orientations?
Yes. The operating position is listed as any position, allowing flexibility when integrating it into a control panel or motor control assembly.
What is the magnetic tripping current?
The magnetic tripping current is 850 A.