steve
Got hold of Sime for a Carrier card for…
Got hold of Sime for a Carrier card for a chiller. Machine down in a factory. Received the new card in express time machine and plant now up and running fantastic service form Sime
1 month ago
Full 12-month warranty
Available for dispatch immediately
We deliver worldwide
1. Email confirmation
You will get an email confirming that we have received your enquiry.
2. Dedicated Account Manager
One of our team will be in touch to confirm your part(s) specification and condition.
3. Your quote
You will receive a comprehensive quote tailored to your specific needs.
All orders are subject to product availability. See our T&Cs.
Ask our team
1. Email confirmation
You will get an email confirming that we have received your enquiry.
2. Dedicated Account Manager
One of our team will be in touch to confirm your part(s) specification and condition.
3. Your quote
You will receive a comprehensive quote tailored to your specific needs.
| Specification | Description |
|---|---|
| Manufacturer | Schneider Electric |
| Part Number | C12B44V160L |
| Product Range | ComPacT NSXm new generation |
| Device Designation | NSXm 160B |
| Product Type | Earth-leakage circuit breaker |
| Application | Electrical power distribution |
| Number of Poles | 4 poles |
| Protected Poles | 4D |
| Neutral Position | Left |
| Rated Current | 160 A at 40 °C |
| Rated Operational Voltage | 440 V AC |
| Network Frequency | 50/60 Hz |
| Isolation Suitability | Suitable for isolation in accordance with IEC 60947-2 |
| Utilisation Category | Category A |
| Ultimate Breaking Capacity | 50 kA at 220–240 V AC; 25 kA at 380–415 V AC; 20 kA at 440 V AC |
| Performance Level | B, 25 kA at 415 V AC |
| Trip Unit | MicroLogic 4.1 electronic trip unit |
| Protection Functions | LSoIR |
| Earth-Leakage Protection | Integrated, Class A and Class AC |
| Earth-Leakage Sensitivity | Adjustable: 30 mA, 100 mA, 300 mA, 500 mA, 1 A, 3 A or 5 A |
| Earth-Leakage Time Delay | Adjustable: 0 ms, 60 ms, 150 ms, 500 ms or 1,000 ms |
| Long-Time Current Setting | Adjustable from 63 A to 160 A across nine settings |
| Short-Time Pick-Up Setting | Adjustable from 1.5 to 10 times Ir across nine settings |
| Instantaneous Pick-Up | Fixed at 2,000 A |
| Thermal Memory | 20 minutes before and after tripping |
| Control Type | Toggle |
| Mounting | Fixed, backplate mounted |
| Mounting Orientation | Horizontal, vertical or flat on the back |
| Connections | Front connection at the upper and lower terminals |
| Terminal Type | EverLink lugs |
| Conductor Capacity | 2.5–70 mm² fine-stranded copper; 2.5–95 mm² rigid or stranded aluminium/copper |
| Rated Insulation Voltage | 500 V AC |
| Impulse Withstand Voltage | 8 kV |
| Mechanical Endurance | 20,000 cycles |
| Power Dissipation | Approximately 12.3 W per pole |
| Auxiliary Capacity | Positions for OF auxiliary switch, SD alarm switch and MN or MX voltage release |
| Degree of Protection | IP40 |
| Impact Resistance | IK07 |
| Operating Temperature | -25 to 70 °C |
| Storage Temperature | -40 to 85 °C |
| Relative Humidity | 0–95% |
| Operating Altitude | Up to 2,000 m without derating; up to 5,000 m with derating |
| Dimensions | 108 mm wide × 144 mm high × 80 mm deep |
| Net Weight | 1.63 kg |
| Colour | Grey, RAL 7016 |
| Applicable Standards | EN/IEC 60947 |
| Pollution Degree | Degree 3 in accordance with IEC 60664-1 |
This is a fixed four-pole earth-leakage circuit breaker from the Schneider ComPacT NSXm range. It is intended for AC electrical distribution and combines overcurrent, short-circuit and earth-leakage protection.
The rated current is 160 A at an ambient temperature of 40°C. Its adjustable long-time current setting covers a range from 63 A to 160 A.
The breaker is fitted with an electronic MicroLogic 4.1 trip unit. It provides adjustable long-time and short-time protection, fixed instantaneous protection and integrated earth-leakage protection.
It has four poles, with all four poles protected. The neutral pole is positioned on the left.
The rated operational voltage is 440 V AC at 50 or 60 Hz. The breaker has a rated insulation voltage of 500 V AC and an impulse withstand voltage of 8 kV.
The ultimate short-circuit breaking capacity is 50 kA at 220–240 V AC, 25 kA at 380–415 V AC and 20 kA at 440 V AC. Its performance level is B, rated at 25 kA at 415 V AC.
Yes. C12B44V160L includes integrated Class A and Class AC earth-leakage protection, with selectable sensitivity settings of 30 mA, 100 mA, 300 mA, 500 mA, 1 A, 3 A and 5 A, depending on the selected class.
Yes. The available earth-leakage time-delay settings are 0 ms, 60 ms, 150 ms, 500 ms and 1,000 ms.
The EverLink terminals accept fine-stranded copper conductors from 2.5 to 70 mm². They also accept rigid or stranded copper and aluminium conductors from 2.5 to 95 mm².
This is a fixed breaker designed for backplate mounting. It may be installed horizontally or vertically, flat against the backplate, with front-accessible upper and lower connections.
The breaker measures 108 mm wide, 144 mm high and 80 mm deep. Its net weight is approximately 1.63 kg, and the enclosure colour is grey, RAL 7016.
The specified ambient operating range is -25°C to 70°C. The storage temperature range is -40°C to 85°C, with a relative humidity range of 0–95%.
The device is rated IP40 in accordance with IEC 60529 and IK07 in accordance with IEC 62262. Its specified pollution degree is 3 under IEC 60664-1.
It can operate at altitudes up to 2,000 metres without derating. Operation up to 5,000 metres is possible with appropriate derating.
The breaker provides positions for an OF auxiliary switch, an SD alarm switch and either an MN undervoltage release or an MX shunt release. A green flag indicates the presence of auxiliary contacts.
The specified mechanical endurance is 20,000 operating cycles. Electrical endurance varies with voltage and load, including 10,000 cycles at 440 V and rated current.
Yes. The C12B44V160L is suitable for isolation in accordance with IEC 60947-2 and is classified as utilisation category A.
The instantaneous current protection threshold is fixed at 2,000 A. The short-time pick-up can be adjusted across nine settings from 1.5 to 10 times the selected long-time current setting.
This content has been produced using multiple sources. EU Automation takes no responsibility for the accuracy of this information. Always consult the original equipment manufacturer for the most up to date instructions and information.
All parts new or reconditioned are covered by EU Automation 12 month warranty
No hassle returns policy
Dedicated customer support team
We understand that credit is a necessary part of business and offer credit agreements on request, subject to status.
Payment optionsWe accept Bank transfers and the following methods of payment:
All transactions are handled securely by HSBC and HSBC Merchant Services. For more information, please visit our dedicated payments page.
Global supplier of quality automation and control components
Dispose of your old unit by exchanging it for a working part.
A comprehensive repair service for faulty equipment.
You don’t need tights and a cape to be a hero.
Get parts fast and feel like a legend, just like Jeff.