Schneider Electric A9R12440 is an Acti9 iID residual current circuit breaker (RCCB) designed to provide earth-leakage protection in three-phase AC distribution systems. This 4-pole, voltage-independent device is rated at 40 A with a 100 mA trip sensitivity (Type AC) and operates at 380 to 415 V AC, 50/60 Hz with instantaneous tripping. It features a clear contact position indicator and a toggle actuator, with DIN rail clip-on mounting for fast installation in modular enclosures. The A9R12440 includes padlocking capability and robust screw terminals that accept top or bottom connections, supporting up to 35 mm² rigid conductors or 25 mm² flexible conductors (with or without ferrules). With compact 8-module width and an operating temperature range of -5 to +60 °C, it is well suited for panel builders and maintenance teams standardizing reliable residual current protection in commercial and industrial switchboards.
Specification Description
Manufacturer Schneider Electric
Part Number A9R12440
Product Range Acti9
Series / Product Name Acti9 iID
Device Type Residual Current Circuit Breaker (RCCB) for earth-leakage protection in AC distribution systems
Poles 4P (4 Pole)
Neutral Position Left
Rated Current (In) 40 A
Rated Operational Voltage (Ue) 380 to 415 V AC
Mains Frequency 50/60 Hz
Network Type AC
Residual Current Sensitivity 100 mA
Residual Current Protection Class Type AC
Time Delay Instantaneous
Tripping Technology Voltage independent
Rated Making & Breaking Capacity (Im / Idm) 1500 A / 1500 A
Rated Conditional Short-Circuit Current 10 kA
Rated Insulation Voltage (Ui) 500 V AC
Impulse Withstand Voltage (Uimp) 6 kV
Control Type Toggle
Contact Position Indicator Yes
Mounting Mode Clip-on
Mounting Support DIN rail
Module Width 8 x 9 mm pitches
Dimensions (H x W x D) 91 mm x 72 mm x 73.5 mm
Net Weight 0.37 kg
Color White
Terminal Type Single terminal, top or bottom
Conductor Capacity (Rigid) 1 to 35 mm²
Conductor Capacity (Flexible) 1 to 25 mm²
Conductor Capacity (Flexible with Ferrule) 1 to 25 mm²
Wire Stripping Length 14 mm
Tightening Torque 3.5 N·m
Locking Provision Padlocking device compatible
Degree of Protection IP20 (device), IP40 (in modular enclosure)
Operating Ambient Temperature -5 to +60 °C
Storage Ambient Temperature -40 to +85 °C
Pollution Degree 3
EMC Impulse Withstand 8/20 µs impulse withstand, 250 A
Standards EN/IEC 61008-1
Product Certification EAC
Country of Origin ES (Spain)
Commodity Code 853620

What is this device used for?

This is a residual current circuit breaker (RCCB) designed to disconnect the circuit when earth-leakage current is detected, helping to reduce the risk of electric shock and to limit leakage-related hazards in AC distribution systems.

What is the rated current of this RCCB?

The rated current is 40 A, meaning it is intended to carry up to 40 A continuously under specified conditions.

How many poles does it have and what does that mean for installation?

It is a 4-pole device (4P), typically used for three-phase plus neutral applications, allowing simultaneous disconnection of all conductors protected by the RCCB.

What is the rated operational voltage and frequency range?

The rated operational voltage is 380 to 415 V AC at 50/60 Hz, suitable for common three-phase low-voltage distribution in that range.

What earth-leakage sensitivity (trip level) does it provide?

It has a 100 mA residual current sensitivity, meaning it trips when the detected leakage current reaches approximately 100 mA (per applicable standard conditions).

Is the tripping time delayed or instantaneous?

It provides instantaneous earth-leakage protection time delay (no intentional time delay).

What does 'Type AC' mean for an RCCB?

Type AC indicates it is designed to operate with residual currents that are sinusoidal AC. It is typically selected for standard AC loads where pulsating DC leakage is not expected.

Does it require a supply voltage to trip on residual current?

No. It uses voltage-independent residual current tripping technology, so the residual current detection/tripping function does not rely on the presence of line voltage.

Where is the neutral positioned on this device?

The neutral position is on the left, which can be important for consistent wiring practices and panel layout.

How is it mounted in a control panel or distribution board?

It is a clip-on device designed for DIN rail mounting and occupies 8 modules (8 x 9 mm pitches).

What are the physical dimensions and approximate weight?

Approximate dimensions are 91 mm (height) x 72 mm (width) x 73.5 mm (depth), with a net weight of about 0.37 kg.

What conductor sizes can be terminated on the terminals?

It supports single-terminal connections (top or bottom): rigid conductors 1 to 35 mm², flexible conductors 1 to 25 mm², and flexible conductors with ferrule 1 to 25 mm².

What are the recommended wiring preparation and terminal tightening values?

The recommended wire stripping length is 14 mm, and the terminal tightening torque is 3.5 N·m for top or bottom connections.

What ingress protection rating does it have?

The device is rated IP20 (per IEC 60529), and it achieves IP40 when installed within a suitable modular enclosure.

What standards does it comply with?

It is designed in accordance with EN/IEC 61008-1 for RCCBs.

What environmental operating and storage temperatures are supported?

Operating ambient temperature range is -5 to +60 °C, and storage temperature range is -40 to +85 °C.

What is the rated conditional short-circuit current?

The rated conditional short-circuit current is 10 kA, which is used when coordinating the RCCB with appropriate upstream protective devices.

Can the handle be locked in position?

Yes. It supports a padlocking device as a locking option, depending on the installation’s lockout requirements and accessory approach.

What are the insulation and impulse withstand ratings?

The rated insulation voltage is 500 V AC, and the rated impulse withstand voltage is 6 kV.

Is there a visual indication of contact position?

Yes. It includes a contact position indicator to show the open/closed status of the contacts.

  • Providing residual-current (earth-leakage) protection on three-phase distribution boards and sub-panels in commercial and light industrial installations
  • Protecting outgoing feeders supplying mixed loads such as small motors, contactor circuits, lighting, and general-purpose power distribution
  • Adding earth-fault protection to four-wire (3P+N) circuits where a left-position neutral is required for consistent panel layouts
  • Segmenting protection across multiple branches to reduce nuisance trips and improve fault isolation within a switchboard
  • Supporting compliance-focused upgrades or retrofits where an AC-type 100 mA RCCB is specified for upstream leakage protection
  • Integrating into modular DIN-rail assemblies for control panels, OEM skids, and packaged equipment power distribution
  • Providing an additional layer of earth-leakage protection on circuits where overcurrent protection is handled by separate protective devices
  • Use in facilities management projects to standardize protective components across sites using Acti9 modular devices

This content has been produced using multiple sources. EU Automation takes no responsibility for the accuracy of this information. Always consult the original equipment manufacturer for the most up to date instructions and information.

Delivery

  • Logistic partners UPS, FedEx and DHL
  • International delivery available
  • Premium nine hour delivery service available to anywhere in Europe
  • Same day dispatch from group stock

Warranty

All parts new or reconditioned are covered by EU Automation 12 month warranty

Returns

No hassle returns policy

Dedicated customer support team

Trade Credit

We understand that credit is a necessary part of business and offer credit agreements on request, subject to status.

Payment options

We accept Bank transfers and the following methods of payment:

All transactions are handled securely by HSBC and HSBC Merchant Services. For more information, please visit our dedicated payments page.

Services

Sourcing your part

Global supplier of quality automation and control components

Service Exchange

Dispose of your old unit by exchanging it for a working part.

Repair

A comprehensive repair service for faulty equipment.

Customer reviews

5 out of 5 stars steve

Got hold of Sime for a Carrier card for…


Got hold of Sime for a Carrier card for a chiller. Machine down in a factory. Received the new card in express time machine and plant now up and running fantastic service form Sime

3 months ago

5 out of 5 stars Daniel

Excellent customer service...


Alex Bailey is my main point of contact at EU Automation...he is extremely friendly, has exceptional customer service skills and always offers great pricing & lead times.

5 months ago

5 out of 5 stars Jerry Schrink

Tom Higgins provided amazing service


Tom Higgins provided great prompt service. I contacted Tom by phone and within 10 minutes there was a quote in my in box. WOW Thank you Tom and Thank you EU Automation!

5 months ago

5 out of 5 stars Paulo Pereira

Excellent service and communication…


Excellent service and communication from Alex Bailey. He truly goes above and beyond to ensure his clients are 100% satisfied. The entire process was seamless, and his attention to detail made a huge difference. Highly recommended for anyone looking for amazing service!

5 months ago

5 out of 5 stars Gary

Tom Higgins did a great job at getting…


Tom Higgins did a great job at getting us the part we needed. He saw a concern with the part a verified before shipping.

5 months ago

5 out of 5 stars Lessle Smith

Thomas Higgins has gone above and…


Thomas Higgins has gone above and beyond to make things happen for my facility. His customer service and knowledge were an asset in helping me with my order and the logistics challenges!

6 months ago

Factory worker carrying automation parts box.

Be a Factory Hero.

Get parts fast.

You don’t need tights and a cape to be a hero.
Get parts fast and feel like a legend, just like Jeff.

Be a Factory Hero

FAQs

View all FAQs

We're here when you need us