steve
Got hold of Sime for a Carrier card for…
Got hold of Sime for a Carrier card for a chiller. Machine down in a factory. Received the new card in express time machine and plant now up and running fantastic service form Sime
2 months ago
Full 12-month warranty
Available for dispatch immediately
We deliver worldwide
1. Email confirmation
You will get an email confirming that we have received your enquiry.
2. Dedicated Account Manager
One of our team will be in touch to confirm your part(s) specification and condition.
3. Your quote
You will receive a comprehensive quote tailored to your specific needs.
All orders are subject to product availability. See our T&Cs.
Ask our team
1. Email confirmation
You will get an email confirming that we have received your enquiry.
2. Dedicated Account Manager
One of our team will be in touch to confirm your part(s) specification and condition.
3. Your quote
You will receive a comprehensive quote tailored to your specific needs.
| Specification | Description |
|---|---|
| Manufacturer | Pilz |
| Part Number | PNOZ MM0P |
| Alternative Part Number | PNOZmm0p |
| Product Type | Configurable compact base unit for the Pilz PNOZmulti Mini control system |
| Function | Provides configurable monitoring and control of machine safeguarding functions such as emergency stop circuits, gate monitoring, reset circuits and related input devices |
| System Range | PNOZmulti Mini |
| Configuration Method | Configured using the PNOZmulti Configurator environment |
| Safety Outputs | 4 semiconductor outputs, O0 to O3 |
| Inputs | 12 digital inputs for devices such as E-STOP pushbuttons, two-hand controls, safety gate switches, reset buttons, light beam devices, scanners, enabling switches and operating mode selector switches |
| Configurable Inputs/Outputs | 8 configurable channels for use as inputs or auxiliary outputs |
| Configurable Outputs | 4 configurable channels for use as auxiliary outputs or test pulse outputs |
| Supply Voltage | 24 V DC |
| Voltage Tolerance | -15% to +20% |
| Power Consumption | 8 W without load; 35 W with load |
| Semiconductor Output Supply | 24 V DC, required even when semiconductor outputs are not used |
| Semiconductor Output Rating | 24 V DC, 2 A per output, 48 W switching capacity |
| Auxiliary Output Rating | 24 V DC, 75 mA |
| Test Pulse Outputs | 4 outputs, 24 V DC, 0.1 A |
| Input Signal Level | Logic 0: -3 to +5 V DC; Logic 1: 15 to 30 V DC |
| Input Current | 5 mA at rated voltage |
| Minimum Pulse Duration | 16 ms |
| Pulse Suppression | 0.6 ms |
| Maximum Input Delay | 4 ms |
| Switch-On Delay | 5 s |
| Switch-Off Delay | 30 ms |
| Supply Interruption Before De-Energisation | 20 ms |
| Status Indication | LED indicators for POWER, RUN, DIAG, FAULT, I FAULT and O FAULT |
| Diagnostics | Displays status and fault information using onboard indicators |
| Chip Card Requirement | Requires a chip card for project storage and operation |
| Connection Terminals | Plug-in spring-loaded or screw terminal options |
| Terminal Conductor Cross Section | 0.20 to 2.50 mm² with spring-loaded terminals; 0.25 to 2.50 mm² single-core flexible with screw terminals |
| Stripping Length | 9 mm for spring-loaded terminals |
| Mounting | 35 mm top-hat rail mounting in a control cabinet |
| Mounting Orientation | Horizontal mounting with ventilation slots facing upwards and downwards |
| Minimum Mounting Clearance | 30 mm above and below; 20 mm to each side from heat-generating devices |
| Enclosure Requirement | Control cabinet protection rating of at least IP54 |
| Housing Protection Rating | IP20 |
| Terminal Protection Rating | IP20 |
| Ambient Operating Temperature | -25 °C to +60 °C |
| Storage Temperature | -25 °C to +70 °C |
| Humidity Rating | 93% relative humidity at 40 °C |
| Vibration Resistance | 10 to 150 Hz, 1 g |
| Shock Resistance | 15 g for 11 ms and 25 g for 6 ms |
| Maximum Operating Altitude | 2,000 m above sea level |
| Dimensions | 100 mm height x 45 mm width x 120 mm depth |
| Weight | 230 g |
| Housing Material | Polycarbonate |
| Approvals | BG, CCC, CE, EAC, TÜV and cULus Listed |
It is a configurable base unit from the PNOZmulti modular safety system, used to monitor machine safety functions and switch semiconductor safety outputs according to a configured safety circuit.
It is commonly used with E-STOP circuits, safety gate monitoring, two-hand controls, reset functions, light beam devices, scanners, enabling switches, operating mode selector switches and similar industrial machine safety functions.
The PNOZ mm0p provides 4 semiconductor safety outputs, designated O0 to O3. Depending on the application design, these can be used for safety functions up to PL e and SIL CL 3.
The unit has 12 dedicated inputs, plus 8 configurable inputs/outputs that can be assigned as inputs or auxiliary outputs depending on the project configuration.
The unit operates from a 24 V DC supply with a voltage tolerance of -15% to +20%. The semiconductor outputs also require a 24 V DC supply, even if those outputs are not being used.
Yes. A chip card is required for operation. The chip card stores the configured project and is inserted into the base unit before commissioning.
Chip cards are available in 8 kByte and 32 kByte memory sizes. For larger projects, the 32 kByte card is generally recommended.
The safety circuit is created using the PNOZmulti Configurator, then transferred to the base unit via chip card or USB connection, depending on the commissioning method being used.
The LEDs indicate key operating states such as power, run status, diagnostics, faults, input faults and output faults. The unit is ready for operation when the POWER and RUN LEDs are lit continuously.
Yes. The unit uses test pulse outputs to monitor shorts across inputs, and it also monitors shorts between the semiconductor safety outputs.
It is designed for installation on a 35 mm DIN rail inside a control cabinet. The cabinet should provide at least IP54 protection, and the unit should normally be mounted horizontally with adequate spacing for heat dissipation.
The unit measures approximately 100 mm high, 45 mm wide and 120 mm deep. The listed weight for the standard PNOZ mm0p is approximately 280 g.
Plug-in connection terminals are used, with either screw terminals or spring-loaded terminals available as accessory terminal sets.
Copper wiring rated for 75 °C should be used. With screw terminals, flexible conductors from 0.25 to 2.50 mm² can be used for a single core, while spring-loaded terminals accept flexible conductors from 0.20 to 2.50 mm².
The wiring should match the configured circuit diagram, the chip card should contain the correct project, the supply voltage should be connected correctly, and the safety devices should be function-tested after a project download or chip card change.
This content has been produced using multiple sources. EU Automation takes no responsibility for the accuracy of this information. Always consult the original equipment manufacturer for the most up to date instructions and information.
All parts new or reconditioned are covered by EU Automation 12 month warranty
No hassle returns policy
Dedicated customer support team
We understand that credit is a necessary part of business and offer credit agreements on request, subject to status.
Payment optionsWe accept Bank transfers and the following methods of payment:
All transactions are handled securely by HSBC and HSBC Merchant Services. For more information, please visit our dedicated payments page.
Global supplier of quality automation and control components
Dispose of your old unit by exchanging it for a working part.
A comprehensive repair service for faulty equipment.
You don’t need tights and a cape to be a hero.
Get parts fast and feel like a legend, just like Jeff.