steve
Got hold of Sime for a Carrier card for…
Got hold of Sime for a Carrier card for a chiller. Machine down in a factory. Received the new card in express time machine and plant now up and running fantastic service form Sime
3 months ago
Full 12-month warranty
Available for dispatch immediately
We deliver worldwide
1. Email confirmation
You will get an email confirming that we have received your enquiry.
2. Dedicated Account Manager
One of our team will be in touch to confirm your part(s) specification and condition.
3. Your quote
You will receive a comprehensive quote tailored to your specific needs.
All orders are subject to product availability. See our T&Cs.
Ask our team
1. Email confirmation
You will get an email confirming that we have received your enquiry.
2. Dedicated Account Manager
One of our team will be in touch to confirm your part(s) specification and condition.
3. Your quote
You will receive a comprehensive quote tailored to your specific needs.
| Specification | Description |
|---|---|
| Manufacturer | Omron |
| Part Number | C200H-DA003 |
| Alternative Part Number | C200HDA003 |
| Product Category | PLC Systems |
| Series | C200H |
| Module Type | Analog output module |
| Number of Outputs | 8 analog output channels |
| Output Signal Ranges | 1 to 5 V, 0 to 10 V, and -10 to +10 V |
| Output Type | Voltage output |
| Resolution | 1/4,000 |
| Configuration | Selectable output voltage range |
| Connection | Removable screw-terminal block |
| Status Indicators | RUN and ERROR indicators |
| Mounting | C200H PLC backplane |
| Description | Eight-channel analog voltage output module designed to convert PLC data into selectable control signals for compatible industrial devices. |
| Commodity Code | 903290 |
The C200H-DA003 is an eight-channel analog voltage output module for Omron C200H-series PLC systems. It converts digital values from the PLC into voltage signals used by compatible field devices.
It provides eight analog voltage output channels, allowing one module to control up to eight compatible devices or process signals.
The module supports 1 to 5 V, 0 to 10 V, and -10 to +10 V output ranges. The required range is configured for each output through the PLC's allocated data memory.
It is an analog output module. The DA designation identifies it as a digital-to-analog unit that sends voltage signals from the PLC to external equipment.
It is designed for use with Omron C200H-family PLC configurations, including supported C200H, C200HS, C200HE, C200HG, and C200HX systems. CPU compatibility and rack capacity should be checked before installation.
Typical uses include providing analog reference signals to variable-frequency drives, valve positioners, process controllers, actuators, indicators, and other equipment that accepts a compatible voltage input.
The module mounts into a compatible C200H backplane slot. Its upper hook is engaged first, after which the module is rotated into position and secured using the lower locking lever.
The PLC exchanges operating data with the module through allocated IR and DM areas. The selected unit number determines which words are assigned to the C200H-DA003.
A rotary unit-number switch on the front of the module assigns its IR and DM word ranges. Each Special I/O Unit in the PLC must have a unique setting to prevent an I/O UNIT OVER error.
A steadily illuminated green RUN indicator shows normal operation, while a flashing RUN indicator identifies adjustment mode. An illuminated red ERROR indicator means the module has detected an error.
Shielded twisted-pair cable is recommended for external output connections. Analog cables should be routed separately from AC wiring, high-voltage cables, main circuits, and other potential sources of electrical interference.
The terminal block accepts crimp-style fork or ring terminals for M3 screws, with a maximum terminal width of 6.0 mm. The specified tightening torque is 0.5 N·m.
Yes. The required output use and signal range are defined through the module's allocated data memory, allowing channels to be configured according to the connected equipment.
Yes. Its output hold function determines the output behavior during operating-state changes or specified PLC conditions. The required behavior should be configured to suit the machine's control sequence.
Yes. The module includes a dedicated adjustment mode for offset and gain calibration. The rear operation-mode switch must be set correctly, and normal mode should be restored before regular operation.
Confirm the full model marking, voltage-output requirement, number of channels, selected signal ranges, unit-number setting, terminal assignments, rack compatibility, and IR/DM configuration. The replacement should match the existing application rather than being selected by appearance alone.
This content has been produced using multiple sources. EU Automation takes no responsibility for the accuracy of this information. Always consult the original equipment manufacturer for the most up to date instructions and information.
All parts new or reconditioned are covered by EU Automation 12 month warranty
No hassle returns policy
Dedicated customer support team
We understand that credit is a necessary part of business and offer credit agreements on request, subject to status.
Payment optionsWe accept Bank transfers and the following methods of payment:
All transactions are handled securely by HSBC and HSBC Merchant Services. For more information, please visit our dedicated payments page.
Global supplier of quality automation and control components
Dispose of your old unit by exchanging it for a working part.
A comprehensive repair service for faulty equipment.
You don’t need tights and a cape to be a hero.
Get parts fast and feel like a legend, just like Jeff.