steve
Got hold of Sime for a Carrier card for…
Got hold of Sime for a Carrier card for a chiller. Machine down in a factory. Received the new card in express time machine and plant now up and running fantastic service form Sime
1 month ago
Full 12-month warranty
Available for dispatch immediately
We deliver worldwide
1. Email confirmation
You will get an email confirming that we have received your enquiry.
2. Dedicated Account Manager
One of our team will be in touch to confirm your part(s) specification and condition.
3. Your quote
You will receive a comprehensive quote tailored to your specific needs.
All orders are subject to product availability. See our T&Cs.
Ask our team
1. Email confirmation
You will get an email confirming that we have received your enquiry.
2. Dedicated Account Manager
One of our team will be in touch to confirm your part(s) specification and condition.
3. Your quote
You will receive a comprehensive quote tailored to your specific needs.
| Specification | Description |
|---|---|
| Part Number | IC695ALG600-DD |
| Manufacturer | GE Fanuc |
| Part Category | Universal Analog Input Module |
| Input Channels | 8 general purpose input channels and 2 Cold Junction Compensation (CJC) channels |
| Input Types | Voltage, current, thermocouple, RTD, and resistance inputs |
| Thermocouple Inputs | Types B, C, E, J, K, N, R, S, T |
| RTD Inputs | PT 385 / 3916, N 618 / 672, NiFe 518, CU 426 |
| Resistance Inputs | 0 to 250 / 500 / 1000 / 2000 / 3000 / 4000 Ohms |
| Current Inputs | 0–20 mA, 4–20 mA, +20 mA |
| Voltage Inputs | +50mV, +150 mV, 0–5 V, 1–5 V, 0–10 V, +10V |
| Backplane Compatibility | RX3i Universal Backplane |
| Power Requirements | 300 mA maximum @ 5.0V, 320 mA maximum @ 3.3V |
| Power Dissipation | 5.4 watts maximum |
| LED Indicators | Module Status, Field Status, and Terminal Block LEDs |
| Module Features | Hot insertion/extraction, terminal block detection, autocalibration, software-configurable, error-checking, open-circuit detection, short-circuit detection for RTDs, user-defined scaling, fault reporting |
| Certifications | CE, UL/CUL 508 and 1604, ATEX |
| Temperature Measurement | Celsius or Fahrenheit |
| Input Resolution | 11 to 16 bits, depending on configured range and A/D filter frequency |
| Configurable Input Filter | 8 Hz, 12 Hz, 16 Hz, 40 Hz, 200 Hz, 1000 Hz |
| Max RTD Cable Impedance | 25 ohm |
| RTD Wire Length | 1000 ft max with settling time of 1mSec |
| Input Impedance | >1M ohm for TC/V/RTD |
| Current Input Resistance | 249 ohm +/- 1% |
| Module Conversion Method | Sigma-delta |
| Isolation Voltage | 250 VAC continuous/1500 VAC for 60 seconds |
| Module Scan Time | 10 ms per Channel × 4 Channels = 40 ms (1K Hz filter), 127 ms per Channel × 4 Channels = 508 ms (8 Hz filter) |
| Calibration Interval | 12 months typical to meet accuracy specifications over time |
| Module Error Over Full Temp Range | 0.5% of range typical, 1.0% of range maximum |
The module can handle a variety of inputs including voltage, current, thermocouple, RTD, and resistance inputs.
This module provides eight general-purpose input channels and two Cold Junction Compensation (CJC) channels.
Yes, each channel can be individually configured for different input types using the Proficy Machine Edition software.
The module supports thermocouple types B, C, E, J, K, N, R, S, and T.
Yes, the module supports hot insertion and extraction, allowing for easy maintenance and upgrades.
The module requires a maximum of 300 mA at 5.0V and 320 mA at 3.3V from the backplane.
The CJC channels are used to improve the accuracy of thermocouple readings by compensating for offset voltages.
The module supports a maximum RTD cable impedance of 25 ohms.
The module offers six hardware analog-to-digital filter frequencies: 8 Hz, 12 Hz, 16 Hz, 40 Hz, 200 Hz, and 1000 Hz.
The module supports overrange, underrange, high alarm, low alarm, high-high alarm, low-low alarm, and calibration fault alarm detection and reporting on a per-channel basis.
This content has been produced using multiple sources. EU Automation takes no responsibility for the accuracy of this information. Always consult the original equipment manufacturer for the most up to date instructions and information.
All parts new or reconditioned are covered by EU Automation 12 month warranty
No hassle returns policy
Dedicated customer support team
We understand that credit is a necessary part of business and offer credit agreements on request, subject to status.
Payment optionsWe accept Bank transfers and the following methods of payment:
All transactions are handled securely by HSBC and HSBC Merchant Services. For more information, please visit our dedicated payments page.
Global supplier of quality automation and control components
Dispose of your old unit by exchanging it for a working part.
A comprehensive repair service for faulty equipment.
You don’t need tights and a cape to be a hero.
Get parts fast and feel like a legend, just like Jeff.