What is this contactor used for?
The ABB 1SBL157001R1301, designated AF12-30-01-13, switches power circuits and controls three-phase motors. Typical applications include motor starters and switching arrangements for non-inductive or slightly inductive loads.
What control voltage does the coil require?
The electronic coil accepts 100–250 V AC at 50/60 Hz or 100–250 V DC. This wide control voltage range accommodates supply variations and allows the same coil version to work with different control voltages within its specified range.
How many main and auxiliary contacts are included?
The contactor has three normally open main contacts and one built-in normally closed auxiliary contact. It does not include a built-in normally open auxiliary contact.
What are the UL/CSA motor horsepower ratings?
The UL/CSA three-phase motor ratings are 3 hp at 200–208 V AC, 3 hp at 220–240 V AC, 7.5 hp at 440–480 V AC, and 10 hp at 550–600 V AC. Single-phase ratings are 1 hp at 120 V AC and 2 hp at 240 V AC.
What are the IEC motor-switching ratings?
For AC-3 duty, the contactor is rated at 12 A and 5.5 kW at 380–400 V AC. Its AC-3 power rating is 3 kW at 220–240 V AC and 7.5 kW at 500 V or 690 V AC. The AC-3 current rating at 690 V is 9 A.
What is the general-use current rating?
The UL/CSA general-use rating is 28 A at 600 V AC. Under IEC AC-1 duty, the rating is 28 A at 690 V with an ambient temperature of 104°F or 140°F (40°C or 60°C), reducing to 24 A at 158°F (70°C). These ratings should not be confused with its AC-3 motor-switching ratings.
What main-circuit voltage can this contactor handle?
The main circuit is rated for operation up to 690 V AC under IEC ratings or 600 V AC under UL ratings. These power-circuit ratings are separate from the coil's 100–250 V AC/DC control voltage range.
Does the contactor include surge suppression?
Yes. The AF electronic coil interface includes built-in surge protection, so an additional coil surge suppressor is not required.
How is the contactor mounted?
The contactor can be installed on a 35 mm DIN rail using either the TH35-7.5 or TH35-15 profile. It also supports panel mounting with two M4 screws positioned diagonally; mounting screws are not supplied.
What are the dimensions and weight?
The contactor measures 45 mm wide, 86 mm high, and 77 mm deep. Its net weight is 0.27 kg.
What type of electrical terminals does it use?
The contactor uses screw terminals for the main, auxiliary, and control circuits. The specified wire-stripping length is 10 mm. UL/CSA tightening torques are 13 in-lb for the main terminals and 11 in-lb for the auxiliary and control terminals.
Can additional auxiliary contacts be fitted?
Yes. The block-type design accepts compatible front- and side-mounted auxiliary contact blocks, allowing additional contacts to be added to suit the control circuit.
What ambient temperature range is permitted?
The specified ambient operating range is -40°F to 158°F (-40°C to 70°C) without a thermal overload relay, or -13°F to 140°F (-25°C to 60°C) when fitted with one. Applicable current derating must also be observed. The storage temperature range is -76°F to 176°F (-60°C to 80°C).
What is the terminal protection rating?
The main, coil, and auxiliary terminals are rated IP20. This terminal rating does not provide protection against water ingress.
What switching frequency is specified?
The maximum electrical switching frequency depends on the duty category: 1,200 cycles per hour for AC-3, 600 for AC-1, and 300 for AC-2 or AC-4. The maximum mechanical switching frequency is 3,600 cycles per hour; this is not the loaded electrical switching limit.