What type of device is this?
This is a thermal overload relay used to help protect electric motors from overload conditions and phase failure in low-voltage control circuits.
What current range can it be set to?
The relay has an adjustable setting range of 1.3 to 1.8 A, making it suitable for motors with a full-load current within that range.
What is the rated operational current?
The rated operational current is 1.8 A, including for AC-3 applications.
How many poles does this overload relay protect?
It is a 3-pole thermal overload relay and protects all three main circuit poles.
What auxiliary contacts are included?
The relay includes 1 normally closed auxiliary contact and 1 normally open auxiliary contact for trip and signalling functions.
What trip class does it use?
It uses trip class 10A, which is commonly used for standard motor overload protection where fast response to overload conditions is required.
Can it be reset manually or automatically?
Yes. The relay has selectable manual or automatic reset, allowing it to be configured to suit the control panel design.
What contactors is it suitable for?
It is suitable for use with A9, A12, A16, A26, A30, A40, AL9, AL12, AL16, AL26, AL30 and AL40 block contactors.
What are the main dimensions?
The product measures approximately 44 mm wide, 80 mm high and 94 mm deep, with a net weight of about 0.15 kg.
What voltage ratings does it have?
The main circuit is rated up to 690 V AC, while the auxiliary circuit is rated up to 500 V AC or 440 V DC.
What degree of protection does the housing provide?
The housing is rated IP20, while the main circuit terminals are rated IP10.
What ambient temperature range is it designed for?
It is designed for operation from -25 °C to +55 °C and storage from -40 °C to +70 °C.
What cable sizes can be connected to the main circuit?
The main circuit accepts flexible or rigid conductors from 0.75 to 4 mm², including ferruled flexible conductors within the same range.
What tightening torque should be used?
The recommended tightening torque is 1.5 to 1.9 N·m for the main circuit and 1.0 to 1.3 N·m for the auxiliary circuit.
What standards is it designed to meet?
It is listed against IEC/EN 60947-1, IEC/EN 60947-4-1, IEC/EN 60947-5-1, UL 60947-1 and UL 60947-4-1 standards.