What type of component is this?
This is a Schneider Multi 9 C60H-DC miniature circuit-breaker designed for direct current distribution circuits. It provides protection against overloads and short-circuits, with switching and isolation functions for suitable DC applications.
What current rating does this circuit-breaker have?
The unit is rated at 3 A at 25 °C, making it suitable for low-current DC feeder or control circuit applications where a C-curve tripping characteristic is required.
How many poles does this device have?
It is a 2-pole device with two protected poles. This configuration is commonly used where both DC polarities need to be protected or isolated.
What voltage range is it designed for?
The rated operational voltage is 12 to 500 V DC. The correct polarity and installation arrangement should be observed according to the application requirements.
What does the C curve mean on this device?
The C curve indicates the tripping behaviour of the circuit-breaker. For this Schneider C60H-DC unit, the magnetic tripping level is specified at approximately 8.5 times the rated current, with a tolerance of ±20%.
What is the breaking capacity of this circuit-breaker?
The breaking capacity depends on the applied DC voltage and standard. It is listed as 20 kA at 220 V DC, 10 kA at 440 V DC, and 6 kA at 500 V DC to EN/IEC 60947-2 and GB 14048.2. Under UL 1077, it is rated 5 kA AIR across 12 to 500 V DC.
Is this device suitable for isolation?
Yes. The Schneider MGN61523 is listed as suitable for isolation according to EN/IEC 60947-2, and it includes ON/OFF indication for local status visibility.
What standards and certifications apply to this component?
The device is associated with UL 1077, GB 14048.2 and EN/IEC 60947-2 standards. Product certifications listed for the unit include UR, CCC and IEC.
How is this circuit-breaker mounted?
It is designed for clip-on DIN rail mounting. Its modular format uses four 9 mm pitches, with approximate dimensions of 81 mm high, 36 mm wide and 73 mm deep.
What terminal connection sizes can it accept?
The tunnel terminals can accept a range of conductor sizes depending on conductor type. Rigid stranded conductors are listed up to 25 mm², while flexible conductors and flexible conductors with ferrules are listed up to 16 mm².
What stripping length and tightening torque are specified?
The specified wire stripping length is 14 mm. The listed tightening torque for the top or bottom terminals is 2.5 N.m, equivalent to approximately 22.13 lbf.in.
What environmental operating range is specified?
The operating ambient air temperature range is -25 °C to 70 °C. For storage, the specified range is -40 °C to 85 °C.
What ingress protection rating does it have?
The device is rated IP20 according to IEC 60529. When installed in a modular enclosure, the protection rating is listed as IP40.
Does it include earth-leakage protection?
No. This unit is specified without earth-leakage protection. It is a miniature circuit-breaker for overcurrent and short-circuit protection in DC circuits.
What is the mechanical and electrical endurance of this device?
The mechanical durability is listed as 20,000 cycles. Electrical durability is listed as 3,000 cycles for L/R = 2 ms applications and 6,000 cycles for resistive circuit conditions.