What type of device is this?
This is a residual current breaker with overcurrent protection (RCBO), specifically the Acti9 iCV40N model from Schneider.
What is the rated current for this device?
The rated current for this device is 20 A.
What is the breaking capacity of this device?
The breaking capacity is 6000 A at 230 V AC 50/60 Hz, conforming to EN/IEC 61009-2-1.
What type of earth-leakage protection does this device offer?
This device offers Type A-SI (Super Immunised) earth-leakage protection with a sensitivity of 30 mA.
What are the dimensions of this device?
The device has a height of 85 mm, a width of 36 mm, and a depth of 73 mm.
Is this device suitable for isolation?
Yes, this device is suitable for isolation, conforming to EN/IEC 60947-2.
What is the IP degree of protection for this device?
The device has an IP20 degree of protection conforming to IEC 60529, and IP40 when installed in a modular enclosure.
What is the operating temperature range for this device?
The operating temperature range is from -25°C to 60°C.
What is the mechanical durability of this device?
The mechanical durability of this device is 20,000 cycles.
What type of terminals does this device use?
This device uses tunnel type terminals for both top and bottom connections, supporting 1…16 mm² rigid and 1…10 mm² flexible wires.