What does this module do in an FX system?
It adds four analogue output channels to a compatible Mitsubishi FX-series PLC system, converting PLC digital values into either voltage or current signals for driving devices such as inverters, valve positioners, and process controllers (FX3U-4DA).
How many analogue outputs are provided, and are they independent?
It provides 4 analogue output channels (CH1 to CH4). Each channel can be configured for the required output type, but the channels are not insulated from each other.
Which output signal ranges are supported?
It supports voltage output (0 to 10 V and also -10 to +10 V depending on configuration) and current output (0 to 20 mA or 4 to 20 mA).
What is the recommended external load for voltage and current outputs?
For voltage output, the external load should be within 1 kΩ to 1 MΩ. For current output, the external load should be 500 Ω or less.
What resolution can I expect from the analogue outputs?
Typical resolution is 0.32 mV for voltage output (20 V span over 64,000 counts) and 0.63 µA for current output (20 mA span over 32,000 counts), depending on the selected output mode.
How accurate are the outputs?
Overall accuracy is typically within ±0.3% of full scale at 25°C (±5°C), and within ±0.5% of full scale over the 0°C to 55°C operating range, assuming correct installation and noise control.
What power supplies are required to run the module?
It requires 24 V DC for the D/A conversion circuit (24 V DC ±10%, 160 mA) and also draws 5 V DC from the PLC (approximately 120 mA).
How is it mounted and how much panel space should be allowed?
It can be DIN-rail mounted (35 mm DIN rail) or directly mounted with M4 screws. The unit body is approximately 55 mm (W) × 90 mm (H) × 87 mm (D), and allowing a small spacing between adjacent units is recommended for installation.
How many PLC I/O points does the module occupy?
It occupies 8 I/O points on the PLC I/O map.
Can I fine-tune the output scaling (offset and gain)?
Yes. Offset and gain adjustment is supported so you can calibrate the output to match field devices; the output resolution does not change when offset/gain is adjusted.
What wiring practices help achieve stable analogue signals?
Use a 2-core twisted, shielded cable for each analogue output run, route analogue cables separately from power/high-voltage wiring, and earth the cable shield at one point on the signal receiving side to minimise noise pickup.
What are the key environmental limits for operation?
The typical operating ambient temperature range is 0°C to 55°C (non-condensing). For best analogue stability, install within a suitable control panel environment and follow good earthing and noise-reduction practices.