What is the power specification for this Power Controller 2 Wide Carrier?
The power specification for the Power Controller 2 Wide Carrier is an input of 30 VDC at a maximum of 8 A.
Can this unit be used in hazardous atmospheres?
Yes, the Power Controller 2 Wide Carrier is suitable for use in hazardous atmospheres and is rated II 3 G, EEx nA IIC T4 according to Nemko No. 02ATEX431U.
What are the environmental specifications for this product?
The environmental specifications include an ambient temperature range of 0 to 60 degrees Celsius, shock resistance of 10g ½ Sinewave for 11 msec, vibration resistance of 1mm Peak to Peak from 5 to 16Hz and 0.5g from 16 to 150Hz, and a relative humidity tolerance of 5 to 95% non-condensing with an IP 20 rating.
Is there a specific procedure for the removal and insertion of this unit?
Yes, the unit cannot be removed or inserted with system power energized. Power must be de-energized before disconnecting any carriers or LocalBus Extender cables. Additionally, a module cover must be fitted to any permanently unoccupied location on a carrier.
Are there any user serviceable parts within this unit?
No, the unit contains no user serviceable parts and should not be disassembled for any reason. Calibration is not required for this product.
What should be done with unoccupied locations on a carrier?
A module cover (KJ4001X1-FA1) must be fitted to any permanently unoccupied location on a carrier, which implies that no system power supply or controller are intended for that location.
What is the maximum allowable length for a combination of I/O carriers and LocalBus Extenders?
The maximum allowable length for a combination of I/O carriers and LocalBus Extenders must not exceed 6.5 meters.
Can this product be unplugged while the system is energized?
The product must not be unplugged unless either the system has been de-energized or the area is known to be non-hazardous.
Does this unit require any calibration?
No, the Power Controller 2 Wide Carrier does not require calibration.
What safety approvals does this product have?
The product has safety approvals including LR87534 and is approved for Class I Division 2, Groups A, B, C, D with a temperature rating of T4.