What is the voltage rating for the local bus power on this electronic part?
The local bus power rating for this part is 12 VDC at 150 mA.
Can this part be used in hazardous atmospheres?
Yes, it is suitable for use in hazardous atmospheres and is rated II 3 G according to ATEX with a Nemko No. 02ATEX431U and EEx nA IIC T4 classification.
What are the environmental specifications for this part?
The part operates within an ambient temperature range of 0 to 60 degrees Celsius, can withstand shock of 10g ½ Sinewave for 11 msec, and vibration of 1mm Peak to Peak from 5 to 16Hz; 0.5g from 16 to 150Hz. It is also rated for airborne contaminants class G3 and has a relative humidity tolerance of 5 to 95% non-condensing with an IP 20 rating.
What is the field circuit rating for this part?
The field circuit rating is 60 VDC at 1.5 A/channel, with a maximum of 6 A per card.
What should be done before removing or inserting this part?
Field power supplied to the device must be removed before removing or connecting the device. Additionally, non-sparking field circuits must be de-energized before removing and inserting the product.
Is there a specific installation instruction for this part?
Yes, there are specific instructions for installation, removal, and operation in hazardous areas. It is important to follow the DeltaV Scalable Process System Zone 2 Installation Instructions for proper handling.
Does this part require calibration?
No, calibration is not required for this part.
What safety approvals does this part have?
This part has safety approvals including LR87534 and is approved for Class I Division 2, Groups A, B, C, D for hazardous locations with a temperature rating of T4.
Can the terminal block fuse be removed with field power energized?
No, a terminal block fuse may not be removed with field power energized for non-sparking circuits.
Are there any user serviceable parts within this part?
No, this unit contains no user serviceable parts and should not be disassembled for any reason.