steve
Got hold of Sime for a Carrier card for…
Got hold of Sime for a Carrier card for a chiller. Machine down in a factory. Received the new card in express time machine and plant now up and running fantastic service form Sime
1 month ago
Full 12-month warranty
Available for dispatch immediately
We deliver worldwide
1. Email confirmation
You will get an email confirming that we have received your enquiry.
2. Dedicated Account Manager
One of our team will be in touch to confirm your part(s) specification and condition.
3. Your quote
You will receive a comprehensive quote tailored to your specific needs.
1. Email confirmation
You will get an email confirming that we have received your enquiry.
2. Dedicated Account Manager
One of our team will be in touch to confirm your part(s) specification and condition.
3. Your quote
You will receive a comprehensive quote tailored to your specific needs.
| Specification | Description |
|---|---|
| Part Number | 6ES7322-8BH10-0AB0 |
| Alternative Part Number | 6ES73228BH100AB0 |
| Manufacturer | Siemens |
| Category | General Automation |
| Description | Siemens SIMATIC S7/PCS7 Series Digital Output Module, capable of diagnostics and wire break detection. It operates with a load voltage of 24 V DC and has 16 digital outputs. |
| Input Current | 100 mA |
| Output Current | 0.6 A |
| Voltage | 24 V DC |
| Dimensions | 40 x 125 x 120 mm |
| Weight | Approximately 350 g |
| Switching Frequency | 100 Hz with resistive load, 10 Hz on lamp load |
| Cable Length | Maximum 1000 m for shielded cables, 600 m for unshielded cables |
| Diagnostics | Yes, includes wire-break, short-circuit, and missing load voltage detection |
| Galvanic Isolation | Yes, between the channels and the backplane bus |
| Connection Method | Requires 1x 40-pin front connector |
| Commodity Code | 853890 |
The input current from load voltage L+ (without load) is a maximum of 100 mA, and from the backplane bus 5 V DC, it is also a maximum of 100 mA.
The typical power loss for this module is 6 W.
This module has 16 digital outputs.
The switching capacity of the outputs on lamp load is a maximum of 5 W.
The output voltage for signal '1' is a minimum of L+ (-0.7 V).
The rated value for the output current for signal '1' is 0.5 A. The permissible range is a minimum of 5 mA and a maximum of 0.6 A.
The maximum switching frequency with resistive load is 100 Hz.
The total current of the outputs per group is a maximum of 2 A for both horizontal installation up to 60 °C and vertical installation up to 40 °C.
Yes, this module has diagnostic functions. It can detect wire-break, short-circuit, and missing load voltage.
The isolation is tested with 500 V DC.
The dimensions of this module are 40 mm in width, 125 mm in height, and 120 mm in depth.
This content has been produced using multiple sources. EU Automation takes no responsibility for the accuracy of this information. Always consult the original equipment manufacturer for the most up to date instructions and information.
All parts new or reconditioned are covered by EU Automation 12 month warranty
No hassle returns policy
Dedicated customer support team
We understand that credit is a necessary part of business and offer credit agreements on request, subject to status.
Payment optionsWe accept Bank transfers and the following methods of payment:
All transactions are handled securely by HSBC and HSBC Merchant Services. For more information, please visit our dedicated payments page.
Pembekal global untuk komponen automasi dan kawalan berkualiti
Dispose of your old unit by exchanging it for a working part.
A comprehensive repair service for faulty equipment.
Discover how we do our part to keep your production lines moving.