What is this contactor used for?
This contactor is used to switch electrical power to loads such as three-phase motors in industrial control circuits. Its DC-operated coil allows a control signal to operate the main power contacts.
How many main poles does this contactor have?
The standard DIL00M-G has three main poles, allowing it to switch the three phases of a motor supply. Auxiliary contacts are separate from these main power contacts.
What control voltage does the coil require?
The catalogue lists a 24 V DC coil version. However, the base designation alone does not establish the coil voltage of every unit, so check the coil marking and full ordering designation before selecting a replacement.
What are the three-phase motor power ratings?
The listed AC-3 motor ratings are 2.2 kW at 220–230 V, 4 kW at 380–400 V and 5.5 kW at 660–690 V. Select the contactor using the motor's operating voltage, current and switching duty rather than power alone.
What is the general-purpose continuous current rating?
The catalogue specifies a general-purpose continuous current rating of 20 A for an open installation and 18 A for an enclosed installation. These values should not be treated as AC-3 motor-switching current ratings.
Are auxiliary contacts included as standard?
The basic DIL00M-G is listed without standard auxiliary contacts. Related versions with the -10 suffix have one normally open auxiliary contact, while versions with the -01 suffix have one normally closed auxiliary contact.
Can additional auxiliary contacts be fitted?
Yes. The catalogue lists top-mounted and side-mounted auxiliary contact modules for this contactor range. Permitted combinations can provide up to five auxiliary contacts, with no more than one side-mounted module on either side. Module compatibility and combination restrictions must be checked before selection.
Does this contactor provide motor overload protection?
The contactor performs the switching function; motor overload protection requires a separate suitable overload relay. The catalogue lists an overload relay as an accessory rather than as part of the basic contactor.
What should be checked when selecting a replacement?
Check the coil voltage, number of main poles, motor rating at the actual supply voltage, auxiliary contact arrangement and terminal layout. Also confirm compatibility with any fitted overload relay or accessory modules, as a similar-looking contactor may have a different electrical configuration.