What is the function of a thermal overload relay?
A thermal overload relay is designed to protect electric motors from overheating, by sensing the current flowing to the motor and breaking the circuit if an overload is detected. It helps prevent damage to the motor that can be caused by excessive current or prolonged overcurrent conditions.
How does the phase failure sensitivity feature work?
The phase failure sensitivity feature of the LR2D1308 ensures that the relay will trip if there is a significant imbalance in the current among the three phases, such as when one phase drops to 30% of the rated current while the others remain at their rated current. This helps protect the motor from potential damage due to phase loss or imbalance.
Can this thermal overload relay be used with different types of circuit protection?
Yes, the LR2D1308 can be used with various types of circuit protection including BS fuses, GB2 circuit breakers, and GG fuses, all rated at 5 A for the control circuit.
What are the mounting options for this relay?
The relay can be mounted on a plate with an EverLink power terminal block or on a rail with an EverLink power terminal block, providing flexibility for different installation requirements.
What is the tripping threshold for this relay?
The tripping threshold for the LR2D1308 is set at 1.14 +/-0.06 times the rated current (In) conforming to IEC 60947-4-1 standards.
What is the operational voltage rating for this relay?
The rated operational voltage for the LR2D1308 is 690 V AC 50/60 Hz for the power circuit, conforming to IEC 60947-4-1 standards.
What are the environmental operating conditions for this relay?
The relay is designed to operate within an ambient air temperature range of -20 to 60 °C and has a fire resistance rating of 850 °C conforming to IEC 60695-2-1. It also has an IP2x degree of protection conforming to VDE 0106.
What certifications does this thermal overload relay have?
The LR2D1308 is certified by multiple international standards, including IEC, UL, CSA, and ATEX, ensuring its compliance with global industry regulations.
What is the significance of the protective treatment TH?
The protective treatment TH indicates that the LR2D1308 has undergone specific treatments to ensure durability and reliability in harsh environments, conforming to IEC 60068.
How is the connection to the control circuit made?
Connections to the control circuit are made using screw clamp terminals that can accommodate cables of 1 to 2.5 mm², with options for both flexible and solid cables, with or without cable ends.