steve
Got hold of Sime for a Carrier card for…
Got hold of Sime for a Carrier card for a chiller. Machine down in a factory. Received the new card in express time machine and plant now up and running fantastic service form Sime
3 weeks ago
Full 12-month warranty
Available for dispatch immediately
We deliver worldwide
1. Email confirmation
You will get an email confirming that we have received your enquiry.
2. Dedicated Account Manager
One of our team will be in touch to confirm your part(s) specification and condition.
3. Your quote
You will receive a comprehensive quote tailored to your specific needs.
1. Email confirmation
You will get an email confirming that we have received your enquiry.
2. Dedicated Account Manager
One of our team will be in touch to confirm your part(s) specification and condition.
3. Your quote
You will receive a comprehensive quote tailored to your specific needs.
| Specification | Description |
|---|---|
| Part Number | GB2CB16 |
| Manufacturer | Schneider |
| Product Type | Motor Circuit Breaker |
| Poles | 1 Pole |
| Rated Current | 10 A |
| Rated Operational Voltage | 277 V ac |
| Network Frequency | 50/60 Hz |
| Breaking Capacity | 2 kA at 110 V ac, 1.5 kA at 230/240 V ac, 1.5 kA at 24 V dc |
| Utilisation Category | Category A, DC-12, DC-13 |
| Mounting Type | DIN Rail Mount |
| Dimensions | 74 x 15 x 67 mm |
| Trip Unit Technology | Thermal-magnetic |
| Magnetic Tripping Current | 138 A |
| Mechanical Durability | 8000 cycles |
| Electrical Durability | 8000 cycles |
| Connection Terminals | Suitable for cables 0.75…6 mm² solid and 0.75…4 mm² flexible with cable end |
| Tightening Torque | 1.2 N.m |
| Operating Altitude | Up to 3000 m |
| Ambient Operating Temperature | -20…60 °C |
| Ambient Storage Temperature | -40…80 °C |
| Degree of Protection | IP20 conforming to IEC 60529 |
| Compliance | EN/IEC 60947-1, EN/IEC 60947-2, CSA C22.2 No 235, UL 1077 |
This is a thermal-magnetic circuit breaker designed for control circuits.
Yes, it is suitable for both AC and DC network types.
The utilisation category is Category A conforming to IEC 60947-2, DC-12 and DC-13 conforming to IEC 60947-5-1.
The rated operational voltage is 277 V AC 50/60 Hz conforming to UL 1077 and CSA C22.2 No 14, and 48 V DC.
The breaking capacity is Icu = 2 kA at 110 V AC 50/60 Hz, Icu = 1.5 kA at 230/240 V AC 50/60 Hz, and Icu = 1.5 kA at 24 V DC, all conforming to IEC 60947-2.
The IP degree of protection is IP20 conforming to IEC 60529.
The ambient air temperature for operation is -20 to 60 °C, and for storage, it is -40 to 80 °C.
The maximum operating altitude is 3000 metres.
It is designed for DIN rail mounting and can be mounted by clips on a plate or rail.
The mechanical and electrical durability are both rated at 8000 cycles.
This content has been produced using multiple sources. EU Automation takes no responsibility for the accuracy of this information. Always consult the original equipment manufacturer for the most up to date instructions and information.
All parts new or reconditioned are covered by EU Automation 12 month warranty
No hassle returns policy
Dedicated customer support team
We understand that credit is a necessary part of business and offer credit agreements on request, subject to status.
Payment optionsWe accept Bank transfers and the following methods of payment:
All transactions are handled securely by HSBC and HSBC Merchant Services. For more information, please visit our dedicated payments page.
Global supplier of quality automation and control components
Dispose of your old unit by exchanging it for a working part.
A comprehensive repair service for faulty equipment.
Discover how we do our part to keep your production lines moving.