steve
Got hold of Sime for a Carrier card for…
Got hold of Sime for a Carrier card for a chiller. Machine down in a factory. Received the new card in express time machine and plant now up and running fantastic service form Sime
1 month ago
Full 12-month warranty
Available for dispatch immediately
We deliver worldwide
1. Email confirmation
You will get an email confirming that we have received your enquiry.
2. Dedicated Account Manager
One of our team will be in touch to confirm your part(s) specification and condition.
3. Your quote
You will receive a comprehensive quote tailored to your specific needs.
1. Email confirmation
You will get an email confirming that we have received your enquiry.
2. Dedicated Account Manager
One of our team will be in touch to confirm your part(s) specification and condition.
3. Your quote
You will receive a comprehensive quote tailored to your specific needs.
| Specification | Description |
|---|---|
| Part Number | 32H8I |
| Alternative Part Number | 32H8I |
| Manufacturer | Eurotherm |
| Series | 3200 Series |
| Type | Indicator and Alarm Unit |
| Supply Voltage | 24 V dc/ac |
| Display | LCD Display |
| Input Types | Universal input, Strain gauge input |
| Output Types | Relay, Analogue (Current and Voltage), Logic |
| Communication | Modbus RTU Slave, EIA 232, EIA 485 |
| Approvals | CE, cUL listed, GOST, FM, EN 14597 TW |
| Environmental Performance | Operating Temperature: 0 to 55°C, Storage: -10 to 70°C, Humidity: 5 to 90% RH non-condensing |
| Panel Sealing | IP65, NEMA 4X |
| Dimensions (WxHxD) | 96 x 48 x 90 mm |
| Panel Mounting Cut Out | 1/8 DIN, horizontal 92W x 45H mm |
| Weight | 350g |
| Power Requirements | 100 to 230V ac, ±15%, 48 to 62 Hz, max 8 W; 24V ac, -15%, +10%; 24V dc -15% +20% |
| Transmitter PSU | 24V dc, 20mA (not on 3216i) |
| Languages Supported | English, French, German, Spanish, Italian |
| Custom Messaging | Up to 15 scrolling text messages, 127 characters max per message |
| Recipes | Up to 5 recipes with 19 parameters |
| Alarm Types | 4 types: Absolute high & low, Rate of change (rising or falling) |
| Calibration Accuracy | <±0.25% of reading ± 1 LSD |
| Input Calibration | User-adjustable over full range, 2-point gain & offset |
| Strain Gauge Sensitivity | 1.4 to 4 mV/V |
| Input Span | –27% to +127% of full scale (approx. –10mV to +50mV) |
| Transducer Excitation | 10V dc + 7% |
| Resolution | Effective bits: >17 for process input, 14.3 for strain gauge input |
| Isolation | 264V ac double insulation from PSU and communication |
The Eurotherm 3200 Series Indicator can accept a wide range of temperature and process inputs, including universal inputs and strain gauge inputs, without the need for any hardware changes. This allows for easy on-site setup and configuration.
Yes, the unit can display custom text messages which can be created with configuration tools and downloaded to the indicator. These messages can provide clear visibility of process events and alarms, aiding operators in understanding and acting upon various conditions.
Yes, the measured process value can be transmitted as either a mA or voltage signal, with a selection of outputs including 4-20mA and 0-10V dc. In the 32H8I model, this signal is isolated from all other electronics within the unit.
The indicator supports both EIA 232 and EIA 485 communication using the Modbus protocol as a slave device. It is also possible to digitally retransmit one parameter using a Modbus broadcast to all other Modbus devices on the network.
Operating parameters can be changed by selecting a recipe using the indicator's push buttons. Recipes can be created with configuration tools and are very useful for processing multiple products that require different parameters.
The indicator is designed to operate within a temperature range of 0 to 55°C and can be stored in temperatures ranging from -10 to 70°C. It has a humidity limit for operation and storage of 5 to 90% RH non-condensing. Additionally, it is sealed to IP65 and NEMA 4X standards, making it suitable for use in various industrial environments.
The indicator holds several certifications including CE, cUL listed, GOST, FM, and EN 14597 TW approval, ensuring compliance with various international standards and regulations.
Yes, the indicator can be used for process interlocks, including over-temperature furnace limits, which are implemented using relay output channels.
The indicator supports scrolling text messages in multiple languages, including English, German, French, Spanish, and Italian, making it versatile for international use.
The 'Alarm Blocking' mode is a special feature that ensures when the unit is powered up, an alarm must first enter a good state before becoming active. This is particularly useful for low alarms which can be blocked while the process is warming up.
This content has been produced using multiple sources. EU Automation takes no responsibility for the accuracy of this information. Always consult the original equipment manufacturer for the most up to date instructions and information.
All parts new or reconditioned are covered by EU Automation 12 month warranty
No hassle returns policy
Dedicated customer support team
We understand that credit is a necessary part of business and offer credit agreements on request, subject to status.
Payment optionsWe accept Bank transfers and the following methods of payment:
All transactions are handled securely by HSBC and HSBC Merchant Services. For more information, please visit our dedicated payments page.
Global supplier of quality automation and control components
Dispose of your old unit by exchanging it for a working part.
A comprehensive repair service for faulty equipment.
Discover how we do our part to keep your production lines moving.