What type of component is this?
The LRD083 is a TeSys Deca differential thermal overload relay designed to protect electric motors against sustained overloads and phase failure.
What is the adjustable current range?
The thermal protection setting can be adjusted from 2.5 A to 4 A, allowing it to be matched to the motor's rated current.
What is the thermal overload trip class?
This relay has a Class 10A trip characteristic in accordance with IEC 60947-4-1.
Which contactors are compatible with this relay?
It is compatible with Schneider TeSys contactor models LC1D09, LC1D12, LC1D18, LC1D25, LC1D32 and LC1D38.
Can it be used with both AC and DC systems?
Yes. The relay is specified for use with both AC and DC network types, with an operating frequency range of 0 to 400 Hz.
What auxiliary contacts are included?
The relay includes one normally open contact and one normally closed contact, identified as a 1 NO + 1 NC auxiliary contact arrangement.
How is the relay reset after it trips?
A blue reset push-button is provided on the unit. It also has a red stop push-button for manual operation.
Does it detect phase failure?
Yes. The LRD083 has phase-failure sensitivity and is specified to trip at 130% of the current setting on two phases when the remaining phase is at zero.
What type of terminals does it use?
It uses spring terminals. The control circuit accepts one solid or flexible conductor from 1 to 2.5 mm², while the power circuit accepts one flexible conductor from 1.5 to 4 mm².
What is the rated operational voltage?
The power circuit has a rated operational voltage of up to 690 V AC at frequencies from 0 to 400 Hz, in accordance with IEC 60947-4-1.
What operating temperature range is specified?
The relay is designed to operate from -20°C to 60°C without derating. Its specified storage temperature range is -60°C to 70°C.
What level of enclosure protection does it provide?
The component has an IP20 ingress protection rating in accordance with IEC 60529.
What are its physical dimensions?
The unit measures approximately 93 mm high, 45 mm wide and 72 mm deep, with a net weight of about 0.14 kg.
How can it be mounted?
It can be fitted directly beneath a compatible contactor. Plate and rail installation are also possible when the appropriate accessories are used.
Which standards does it conform to?
The relay is designed in accordance with relevant standards including EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, UL 60947-5-1 and applicable CSA standards.