What type of electrical device is this?
It is a SENTRON on/off switch disconnector designed to provide manual switching and isolation of an AC electrical circuit.
What is the rated operational current?
The switch disconnector has a rated operational current of 125 A.
What operating voltage does it support?
The device is rated for operation at up to 440 V AC with a frequency of 50 or 60 Hz.
How many poles does the switch disconnector have?
It is a four-pole device with four normally open contacts, allowing four conductors to be switched together.
What is the short-circuit current rating?
The specified short-circuit current rating is 10 kA when the device is installed under the appropriate system conditions.
What is the rated switching capacity?
The rated switching capacity is 0.375 kA, equivalent to 375 A.
What conductor sizes can be connected?
The terminals accept rigid or flexible conductors with prepared ends from 2.5 mm² to 50 mm².
What terminal tightening torque is required?
The specified tightening torque for the screw terminals is between 2.5 N·m and 3 N·m.
How much panel space does the device require?
The 5TL1492-0 occupies four modular width units, making it suitable for installation in compatible modular distribution assemblies.
What are the device dimensions?
The unit measures approximately 89.8 mm in height and 74.5 mm in depth, with an installation depth of 70 mm.
How much does the switch disconnector weigh?
The net weight is approximately 443 g.
What operating temperatures are permitted?
The specified ambient operating temperature range is from -5°C to 40°C. The minimum storage temperature is -25°C.
Does the device include an indicator lamp?
No, this model does not include an integrated signal lamp.
How much power does the device dissipate?
At the rated AC current in a hot operating state, the stated power loss is 8.6 W per pole.
Does the switch provide positive opening in accordance with DIN VDE 0113?
No, positive opening in accordance with DIN VDE 0113 is not specified for this model.
What applications is this switch disconnector suited to?
It is suited to AC distribution and control assemblies that require four-pole manual on/off switching and circuit isolation within its specified 125 A and 440 V AC ratings.