What type of electrical accessory is this?
This is a left-side shunt trip accessory for Siemens SENTRON 3VA moulded case circuit breakers. It is used to trip a compatible breaker electrically from a remote control signal.
What is a shunt trip used for?
A shunt trip is used to open a circuit breaker when an external voltage is applied to the trip coil. Common uses include remote disconnection, emergency-off circuits, interlocking arrangements and automated panel control.
Which breaker ranges is it designed for?
It is intended as an accessory for Siemens 3VA4, 3VA5 and 3VA6 moulded case circuit breakers, subject to the correct frame size and accessory mounting position.
What does the left-side designation mean?
The left-side designation indicates that the accessory is fitted in the left-hand accessory location of the compatible breaker. The mounting position should be checked against the breaker configuration before installation.
What control voltage does it use?
This shunt trip is rated for 208 to 277 V AC at 50/60 Hz, and 220 to 250 V DC. For 3VA9978-0BL33, the maximum apparent power consumption is 40 VA and the maximum DC active power consumption is 35 W.
Can it be used on both AC and DC control circuits?
Yes. The accessory is suitable for the specified AC and DC control voltage ranges: 208 to 277 V AC at 50/60 Hz, or 220 to 250 V DC.
What are the main dimensions?
The unit measures approximately 65.1 mm high, 25.7 mm wide and 31.2 mm deep. Its net weight is approximately 91 g.
What wiring size can be connected?
For IEC wiring, the connectable conductor cross-section is 0.5 to 1.5 mm². The coded AWG range for auxiliary contacts is AWG 20 to AWG 16.
What stripped conductor length is required?
The specified stripped conductor length is 10 mm, equivalent to 0.4 in.
What terminal tightening torque should be used?
For screw-type terminals, the tightening torque range is 0.4 to 0.5 N·m. In imperial units, this is 3.5 to 4.4 lbf·in.
What insulation and surge ratings does it have?
The rated insulation voltage is 690 V, with a surge voltage resistance of 4 kV. It is also listed with overvoltage category III and pollution degree 3.
Is it a main breaker or an accessory?
It is an auxiliary release accessory, not a standalone circuit breaker. It must be installed into a compatible Siemens 3VA breaker to perform its intended tripping function.