What is the function of this circuit breaker?
The circuit breaker is designed for motor protection and features a Class 10 overload protection. It is equipped with a transverse auxiliary switch and is intended to safeguard electrical circuits from damage caused by overloads or short circuits.
Can this circuit breaker be used in hazardous locations?
Yes, this circuit breaker has approvals for use in hazardous locations, ensuring it can be safely deployed in environments with potentially explosive atmospheres.
What are the mounting options for this circuit breaker?
The circuit breaker can be mounted using screw and snap-on mounting onto a 35 mm standard mounting rail according to DIN EN 60715, allowing for versatile installation options.
What type of terminals does this circuit breaker have?
This circuit breaker is equipped with spring-loaded terminals for both the main current circuit and auxiliary and control current circuits, facilitating secure and reliable connections.
What is the maximum operating voltage for this circuit breaker?
The maximum operating voltage for the circuit breaker is rated at 690 V, suitable for a wide range of industrial applications.
What is the temperature range for operating this circuit breaker?
The circuit breaker can operate within an ambient temperature range of -20 to +60 degrees Celsius, ensuring reliable performance in various environmental conditions.
What is the mechanical service life of the main contacts for this circuit breaker?
The main contacts of the circuit breaker have a typical mechanical service life of 100,000 switching cycles, indicating a robust and durable design.
What is the trip class of this circuit breaker?
This circuit breaker has a trip class of CLASS 10, which refers to its ability to trip within 10 seconds at 600% of its rated current, providing fast protection against overloads.
Is there a specific screwdriver size required for the terminals?
Yes, the terminals require a screwdriver with a tip size of 3.0 x 0.5 mm for secure and proper installation.
What is the B10 value for this circuit breaker?
The B10 value, which indicates the number of operations before 10% of components may fail, is 5,000 for this circuit breaker when used at a high demand rate according to SN 31920.