What does this power contactor do in a control panel?
It is an electromechanical switching device used to connect and disconnect a three-phase power circuit (typically a motor feeder) using a low-voltage control signal.
What is the rated operational current and application category?
It is rated up to 16 A in AC-3 duty (motor switching) at 400 V, and 22 A in AC-1 duty (resistive/low-inductance loads) at 400 V (at 40 °C ambient).
What motor power can it switch?
For typical motor switching (AC-3), it is suitable for up to 7.5 kW at 400 V.
What coil voltage does it require?
The control coil is 24 V DC, with an operating range factor of 0.8 to 1.1 of rated voltage.
Does the coil include surge suppression?
Yes. The coil has an integrated diode for surge suppression. Because it is diode-based, correct polarity must be observed when wiring the coil terminals (A1 positive, A2 negative).
How many main power poles and main contacts are provided?
It is a 3-pole contactor with 3 normally-open (NO) main contacts for switching a three-phase circuit.
What auxiliary contacts are included?
It includes a captive (built-in) auxiliary contact set of 2 NO + 2 NC instantaneous contacts for control and signalling duties.
What are the auxiliary contact ratings for control circuits?
Typical auxiliary ratings include AC-15: 6 A at 230 V and 3 A at 400 V; DC-13: 6 A at 24 V, 1 A at 110 V, and 0.3 A at 220 V.
What is the insulation and voltage capability of the main circuit?
The rated insulation voltage is 690 V, and the impulse voltage withstand is 6 kV.
What ingress protection does it provide?
The front protection class is IP20, with finger-safe touch protection from the front.
How is it mounted in an enclosure?
It is suitable for screw mounting or snap-on mounting onto a 35 mm standard DIN rail (DIN EN 60715). Side-by-side mounting is permitted (0 mm side spacing), with recommended clearance to the front/up/down as specified by the installation guidelines.
What are the approximate dimensions?
Overall dimensions are approximately 45 mm wide, 58 mm high, and 117 mm deep.
What cable sizes can be connected to the terminals?
Main and auxiliary screw terminals accept solid or stranded conductors typically from 0.5 to 4 mm² (fine-stranded with end sleeves typically 0.5 to 2.5 mm²).
What is the typical mechanical endurance?
Typical mechanical life is about 10,000,000 operating cycles for the contactor mechanism.
Are there recommendations for short-circuit protection coordination?
Yes. Typical gG fuse guidance for the main circuit is 50 A for coordination type 1 and 25 A for coordination type 2 (exact selection depends on prospective short-circuit current and installation conditions).
How should I describe this item on documentation or a bill of materials?
A clear description is: three-pole power contactor, size S00, 24 V DC coil with integrated diode, AC-3 16 A (7.5 kW at 400 V), built-in 2NO+2NC auxiliary contacts. If needed, you can add the ordering reference 3RT2018-1FB44-3MA0 in the line item.