What is the size of the contactor?
The contactor is of size S12, which is a designation used by Siemens to indicate the physical and electrical capacity of the contactor.
What is the protection class of the contactor on the front?
The protection class on the front of the contactor is IP00, which means it is not protected against any ingress of solid objects or water. It is advisable to install it within a secure enclosure for protection.
Can this contactor be used in safety-related applications?
Yes, the contactor is suitable for safety-related switching OFF applications, as it features a mirror contact according to IEC 60947-4-1.
What are the operational current ratings for this contactor?
The operational current ratings for the contactor at AC-3 at 400 V are rated at 400 A. It also has different current ratings for other AC and DC applications, which can be found in the detailed specifications.
What type of connections does the contactor support?
The contactor supports a connection bar for the main current circuit and screw-type terminals for auxiliary and control circuits, as well as for the magnet coil.
What are the dimensions of the contactor?
The contactor has a height of 214 mm, a width of 160 mm, and a depth of 225 mm.
What is the mechanical service life of the contactor?
The mechanical service life of the contactor is typically 10 million operating cycles, which can vary with the addition of auxiliary switch blocks.
What is the ambient temperature range for operating this contactor?
The contactor can operate within an ambient temperature range of -25 to +60 degrees Celsius.
Is side-by-side mounting possible with this contactor?
Yes, side-by-side mounting is possible with this contactor, allowing for efficient use of space within control cabinets.
What is the required spacing for side-by-side mounting?
When mounting side-by-side, a spacing of 20 mm forwards, 10 mm upwards, and 10 mm downwards is required. There is no additional spacing required at the side.