What are the main characteristics of this Siemens Power Contactor?
This Siemens Power Contactor is designed for switching motors and has an AC-3 rating of 50 A and 22 kW at 400 V. It features a control supply voltage of 230 V AC at 50 Hz, 3 poles, and is a size S2 with screw terminal connections. It also includes 2 normally open (NO) and 2 normally closed (NC) auxiliary contacts.
Can this contactor be used for high inductive loads?
Yes, the contactor is suitable for high inductive loads, with an operating current at AC-1 of 60 A at 400 V, making it capable of handling significant inductive loads at the rated voltage.
What is the insulation voltage rating of this contactor?
The insulation voltage rating of the contactor is 690 V, which is the rated value for the dielectric strength of the insulating material used in the contactor.
What type of mounting can be used with this contactor?
The contactor supports both screw and snap-on mounting onto a 35 mm standard mounting rail according to DIN EN 50022, allowing for flexible installation options.
What is the mechanical service life of the contactor?
The mechanical service life of the contactor is typically 10 million switching cycles, indicating its durability and longevity in operational use.
What are the dimensions of this contactor?
The dimensions of the contactor are 112 mm in height, 55 mm in width, and 164 mm in depth, which corresponds to the size S2 classification.
What is the protection class of the contactor?
The protection class for the front of the contactor is IP20, and for the terminal, it is IP00, indicating the level of protection against ingress of solid objects and moisture.
What is the operating temperature range for this contactor?
The operating temperature range for the contactor is from -25°C to +60°C, ensuring reliable performance across a wide range of environmental conditions.
What is the surge voltage resistance of this contactor?
The surge voltage resistance of the contactor is rated at 6 kV, which refers to its ability to withstand transient voltage spikes without damage.
How can I determine if this contactor is suitable for my application?
To determine suitability, you should compare your application's requirements with the contactor's rated operating current, voltage, power, and auxiliary contact configurations, as well as environmental and mechanical specifications.