What is the purpose of this motor starter?
The Siemens SIRIUS Series DOL Motor Starter is designed for starting and stopping electric motors. It provides electronic overload protection to prevent damage to the motor due to excessive current draw.
Can this motor starter be used with any motor?
It is suitable for use with three-phase motors that have a power range of 0.09 to 0.75 kW and an operating current of 0.4 to 2 A at 400 V in a 50 Hz power system.
What type of protection does this motor starter offer?
This motor starter offers electronic overload protection with a trip class of CLASS 10A, ensuring the motor is protected against excessive current draw.
What is the installation altitude limit for this device?
The motor starter can be installed at altitudes up to 4,000 meters above sea level without derating.
What are the ambient temperature limits for operating this motor starter?
The device can operate within an ambient temperature range of -25 to +60 degrees Celsius.
What is the IP rating of this motor starter?
The motor starter has an IP20 rating, indicating protection against solid objects larger than 12.5 mm but not against liquids.
How can this motor starter be mounted?
It can be mounted on a DIN rail with either screw or snap-on mounting options, providing flexibility for installation.
What is the significance of the trip class for this motor starter?
The trip class, CLASS 10A, refers to the thermal memory and response time of the overload protection, which in this case will trip the device within 10 seconds under certain conditions to protect the motor.
What are the dimensions of this motor starter?
The dimensions of the motor starter are 141.6 x 22.5 x 100 mm, making it compact and suitable for installations where space is limited.
Is there a specific type of terminal connection for this motor starter?
Yes, it uses screw-type terminal connections for both the main circuit and the control circuit, ensuring secure and reliable connections.