What is the rated current for this LV HRC fuse element?
The rated current for this low-voltage high rupturing capacity (LV HRC) fuse element is 400 A.
Can this fuse element be used with both AC and DC voltages?
Yes, this fuse element is suitable for both AC and DC applications. It has a rated voltage of 500 V for AC and 440 V for DC.
What is the operating class of this fuse link?
The operating class of this fuse link is gG, which is suitable for general applications, providing both overload and short-circuit protection.
Does this fuse element come with any indication feature?
Yes, it features a front indicator that provides a visual indication when the fuse has operated.
What is the size of this fuse system according to DIN EN 60269-1?
According to DIN EN 60269-1, the size of this fuse system is NH3.
What type of contacts does this fuse link have?
This fuse link is designed with non-corroding, silver-plated blade contacts.
What is the protection class IP rating of this fuse element?
The protection class IP rating of this fuse element is IP20, with connected conductors.
What are the mounting requirements for this fuse link?
The fuse link is designed for mounting with non-insulated grip lugs and can be positioned in any orientation, though vertical is preferable.
What is the ambient temperature range for operating this fuse element?
The ambient temperature range for operating this fuse element is from -5 °C to +40 °C.
What is the switching capacity of this fuse link?
The switching capacity of this fuse link is 120 kA according to IEC 60947-2 for AC, and 25 kA for DC applications.