What is this component used for?
This replacement contactor coil energises the electromagnetic mechanism of a compatible contactor, enabling its contacts to change state. The LX1D6U7 belongs to the TeSys Deca range and is supplied as a coil rather than a complete contactor.
What control voltage and frequency does the coil require?
The coil is rated for a 240 V AC control supply at either 50 Hz or 60 Hz. It is not specified for operation from a DC supply.
Which contactors are compatible with this coil?
The specified compatible contactor models are LC1D80 and LC1D95. Check the contactor reference and required control voltage before selecting this replacement coil.
Do the 80 A and 95 A ratings describe the coil current?
No. These ratings identify the contactor sizes for which the coil is intended. The coil itself has a nominal control voltage of 240 V AC, with consumption specified separately for energisation and holding.
Does the coil include a built-in suppression module?
No. The LX1D6U7 does not have a built-in suppressor module. Any requirement for external suppression should be assessed against the control circuit and compatible contactor accessories.
What are the inrush and holding power requirements?
At 20 °C, the specified inrush apparent power is 245 VA and the holding apparent power is 26 VA. These figures apply at both 50 Hz and 60 Hz and distinguish the initial energisation demand from the demand once the contactor is held closed.
What operating voltage tolerances are specified?
At ambient temperatures below 55 °C, the operational voltage range is 0.8 to 1.1 times the rated control voltage at 50 Hz, or 0.85 to 1.1 times the rated control voltage at 60 Hz.
What is the specified drop-out voltage range?
At temperatures below 55 °C, the drop-out range is 0.3 to 0.6 times the rated control voltage at either 50 Hz or 60 Hz.
What ambient temperature range is specified for operation?
The specified operating ambient temperature range is -5 °C to +60 °C. The stated operational voltage tolerances apply at temperatures below 55 °C.
What are the coil resistance and inductance values?
The average resistance is 131 ohms at 20 °C, and the closed-circuit inductance is 8.3 H. The resistance figure is a temperature-specific reference value rather than an operating current rating.
How much heat does the coil dissipate?
The specified heat dissipation is 6 to 10 W at 50/60 Hz. This heat contribution should be considered when assessing the thermal conditions inside the control enclosure.
What maximum operating rate is listed?
The product data lists a maximum operating rate of 3,600 cycles per hour at 60 °C. Suitability for a particular switching duty also depends on the complete contactor and its application.
What is the net weight of the coil?
The coil has a net weight of 0.28 kg, excluding packaging.