What is the main function of this circuit breaker?
The GV2ME32 circuit breaker is primarily used for motor protection. It is designed to protect an electrical circuit from damage caused by excess current from an overload or short circuit.
What are the key specifications of this circuit breaker?
This circuit breaker has 3 poles, a rated current of 32 A, and a rated operational voltage of 690 V ac. It is designed for DIN Rail Mount and has a breaking capacity of 3 kA at 690 V ac. The dimensions are 45 x 78.2 x 89 mm.
What is the trip unit technology used in this circuit breaker?
The GV2ME32 circuit breaker uses thermal-magnetic trip unit technology. This means it combines two types of protection: thermal for overload and magnetic for short circuit.
What is the thermal protection adjustment range of this circuit breaker?
The thermal protection adjustment range of the GV2ME32 circuit breaker is 24 to 32 A, according to IEC 60947-4-1.
What is the breaking capacity of this circuit breaker?
The GV2ME32 circuit breaker has a breaking capacity of 3 kA at 690 V AC, according to IEC 60947-2.
What is the rated insulation voltage of this circuit breaker?
The rated insulation voltage of the GV2ME32 circuit breaker is 690 V AC at 50/60 Hz, according to IEC 60947-2.
What is the power dissipation per pole of this circuit breaker?
The power dissipation per pole of the GV2ME32 circuit breaker is 2.5 W.
What is the mechanical durability of this circuit breaker?
The GV2ME32 circuit breaker has a mechanical durability of 100,000 cycles.
What is the electrical durability of this circuit breaker?
The GV2ME32 circuit breaker has an electrical durability of 100,000 cycles for AC-3 at 415 V In.
What is the tightening torque of this circuit breaker?
The tightening torque of the GV2ME32 circuit breaker is 1.7 N.m for screw clamp terminal.