What is the main function of this part?
The GV2ME22 is a Motor Protection Circuit Breaker. It is designed to protect an electrical motor from damage caused by overloads, short circuits, or phase failures.
What are the key specifications of this part?
This part has a rated current of 25 A, a thermal protection adjustment range of 20-25 A, and a rated operational voltage of 690 V AC 50/60 Hz. It also has a breaking capacity of 50 kA Icu at 230/240 V AC 50/60 Hz.
What type of mounting does this part support?
The GV2ME22 supports DIN Rail Mounting, making it easy to install in a variety of settings.
What is the operating temperature range for this part?
The GV2ME22 can operate effectively in ambient air temperatures ranging from -20 to 60 degrees Celsius.
What is the significance of the part's thermal-magnetic tripping technology?
The thermal-magnetic tripping technology in the GV2ME22 allows it to protect motors by tripping in response to both thermal (overload) and magnetic (short-circuit) faults. This dual protection ensures the safety and longevity of your motor.
What is the power dissipation per pole for this part?
The GV2ME22 has a power dissipation of 2.5 W per pole.
What is the control type of this part?
The GV2ME22 uses a push-button control type.
What is the product's environmental profile?
The GV2ME22 is a Green Premium product, meaning it complies with environmental standards such as REACh and RoHS.