What are the main characteristics of this power contactor?
The power contactor is a 3-pole device with 3 normally open (NO) contacts, rated for 9 A operating current at AC-3 400 V, and has a control voltage of 24V DC. It's designed for a power rating of 4 kW at 400 V in AC-3 applications and is suitable for mounting onto a 35 mm standard mounting rail according to DIN EN 50022.
Can this contactor be installed in any orientation?
The contactor is designed for vertical mounting positions to ensure proper operation and longevity.
What is the size of this contactor and how much space is required for installation?
The contactor is of size S0, with dimensions of 45 mm in width, 85 mm in height, and 100 mm in depth. A spacing of 6 mm to earthed parts is required at the side for proper installation.
What type of terminals does this contactor have for electrical connections?
This contactor features screw-type terminals for the main current circuit and spring-loaded terminals for the auxiliary and control current circuit.
What is the mechanical service life of this contactor?
The mechanical service life of the contactor is typically 10 million operating cycles, which can vary when auxiliary switch blocks are added.
What is the ambient temperature range for operating this contactor?
The contactor can operate within an ambient temperature range of -25 to +60 degrees Celsius.
What is the IP protection class of this contactor?
The contactor has an IP20 protection class on the front, indicating protection against solid objects larger than 12.5 mm but not against water.
What is the maximum installation altitude for this contactor?
The maximum installation altitude for the contactor is 2,000 meters above sea level.
How is the contact reliability of the auxiliary contacts rated?
The contact reliability of the auxiliary contacts is rated at 1 faulty switching per 100 million at 17 V, 1 mA.
What type of protection is required for the contactor's circuits?
For short-circuit protection of the main circuit, a fuse gL/gG with a rating of 63 A is required for type of coordination 1, and 25 A for type of coordination 2. For the auxiliary switch, a fuse gL/gG of 10 A is required.