What type of circuit protection does this device provide?
The A9F85201 is an Acti9 iC60H miniature circuit breaker with thermal-magnetic protection. It protects distribution circuits against overloads and short circuits and has a rated current of 1 A.
How many poles does this circuit breaker protect?
This is a two-pole circuit breaker with protection on both poles. Its 2P configuration provides linked switching of the two poles.
What tripping characteristic does this circuit breaker have?
It has a D-curve tripping characteristic. The datasheet specifies a magnetic tripping limit of 12 times the rated current, with a tolerance of ±20%. This characteristic must be considered when coordinating the breaker with the circuit’s starting currents and fault conditions.
Can this circuit breaker be used in AC and DC circuits?
Yes. The A9F85201 is specified for both AC and DC networks, with a frequency of 50/60 Hz for AC operation. Breaking capacities differ according to the voltage, network type and applicable standard, so the relevant rating must be checked for the intended circuit.
What is the short-circuit breaking capacity?
The rated short-circuit capacity, Icn, is 10 kA at 400 V AC under IEC/EN 60898-1. Under IEC/EN 60947-2, the ultimate breaking capacity, Icu, is 70 kA at the listed AC voltage ranges up to 440 V, and 15 kA for DC applications up to 125 V. These ratings apply under their respective specified conditions.
How is this circuit breaker mounted, and how much space does it require?
The breaker mounts on a DIN rail and measures 85 mm high, 36 mm wide and 78.5 mm deep. Its width occupies four 9 mm pitches, making these dimensions useful when planning space within a distribution board or enclosure.
What conductor sizes can the terminals accommodate?
The top and bottom terminals accept rigid conductors from 1 to 25 mm² and flexible conductors from 1 to 16 mm². The specified wire stripping length is 14 mm, and the terminal tightening torque is 2 N·m.
Is it compatible with comb busbars?
Yes. The datasheet lists comb busbar and distribution block compatibility at both the top and bottom connections. The selected busbar or distribution block must be suitable for the breaker and the intended assembly.
Does this circuit breaker include earth-leakage protection?
Earth-leakage protection is not built into the circuit breaker. The datasheet specifies a separate block for this function, so applications requiring residual-current protection need an appropriately selected additional device.
What environmental operating limits are specified?
The specified ambient operating temperature is −35°C to +70°C, with a storage temperature range of −40°C to +85°C. The stated operating altitude is 0 to 2,000 metres, and the degree of protection is IP20.
Does the breaker provide visible status indication?
Yes. It includes a contact position indicator and a local trip indicator. A toggle provides manual operation.
What mechanical and electrical endurance ratings are listed?
The datasheet lists mechanical endurance of 20,000 operating cycles and electrical endurance of 10,000 operating cycles. These are endurance ratings rather than a prediction of operating life in a particular installation.