What is this unit used for?
The RPS 80 EEC is a 24 V DC DIN rail power supply unit designed for industrial control cabinets and Ethernet infrastructure. It converts a wide AC or DC input into a regulated 24 V DC output for compatible industrial devices.
What input voltage range can the unit accept?
It accepts 100 to 240 V AC, ±15%, at 50 to 60 Hz, or 110 to 300 V DC with a -20% to +25% tolerance. This makes it suitable for a broad range of industrial power systems.
What output voltage does the unit provide?
The output is externally adjustable from 24 to 28 V DC, with a typical setting of 24.1 V DC.
What output current is available?
The unit provides 3.4 to 3.0 A continuous output current, depending on operating conditions. It can also provide a short-term output of at least 5.0 to 4.5 A for approximately 4 seconds.
How is the unit installed in a panel?
It is designed for 35 mm DIN rail mounting, making it suitable for standard industrial enclosures and control panels.
What are the dimensions of the unit?
The unit measures 32 mm wide, 124 mm high and 102 mm deep, allowing it to fit into compact control cabinet layouts.
What type of electrical terminals does it use?
It has one 3-pin bi-stable quick-connect spring clamp terminal for voltage input and one 4-pin bi-stable quick-connect spring clamp terminal for voltage output.
Can more than one unit be connected in parallel?
Yes. The power supply units can be connected in parallel, which is useful when designing redundant 24 V DC power arrangements.
What status indication is built into the unit?
The unit includes LED indication for DC OK and Overload, helping panel users quickly identify the operating state.
What operating temperature range is specified?
The specified operating temperature range is -25 °C to +70 °C. Derating applies from 60 °C.
What is the enclosure protection rating?
The unit has an IP20 protection rating, which is typical for equipment intended for installation inside an industrial cabinet or enclosure.
What approvals are associated with the unit?
The unit is listed with approvals including CE, cUL 508, cUL 60950-1 and Germanischer Lloyd, with hazardous location approval noted as pending in the referenced product information.