steve
Got hold of Sime for a Carrier card for…
Got hold of Sime for a Carrier card for a chiller. Machine down in a factory. Received the new card in express time machine and plant now up and running fantastic service form Sime
3 months ago
Full 12-month warranty
Available for dispatch immediately
We deliver worldwide
1. Email confirmation
You will get an email confirming that we have received your enquiry.
2. Dedicated Account Manager
One of our team will be in touch to confirm your part(s) specification and condition.
3. Your quote
You will receive a comprehensive quote tailored to your specific needs.
All orders are subject to product availability. See our T&Cs.
Ask our team
1. Email confirmation
You will get an email confirming that we have received your enquiry.
2. Dedicated Account Manager
One of our team will be in touch to confirm your part(s) specification and condition.
3. Your quote
You will receive a comprehensive quote tailored to your specific needs.
| Specification | Description |
|---|---|
| Manufacturer | Square D |
| Part Number | BGA36080 |
| Product Range | PowerPact B |
| Product Type | Thermal-magnetic circuit breaker for electrical distribution |
| Rated Current | 80 A |
| Number of Poles | 3 |
| AC Voltage Rating | 600Y/347 V AC |
| Network Frequency | 50/60 Hz |
| Trip Technology | Thermal-magnetic tripping for overload and short-circuit protection |
| Continuous Current Rating | 80% |
| Breaking Capacity at 208Y/120 V AC | 65 kA, UL 489 |
| Breaking Capacity at 240 V AC | 65 kA, UL 489 |
| Breaking Capacity at 480 V AC | 35 kA, UL 489 |
| Breaking Capacity at 600Y/347 V AC | 18 kA, UL 489 |
| Breaking Capacity at 250 V DC | 20 kA, UL 489 |
| Rated Insulation Voltage | 800 V, IEC 60947-2 |
| Rated Impulse Withstand Voltage | 8 kV, IEC 60947-2 |
| Mounting Type | I-Line mounting |
| Electrical Connections | I-Line connection on the incoming side; cable lugs on the outgoing side |
| Phase Connection | ABC |
| Operating Mechanism | Toggle handle |
| Conductor Compatibility | Copper or aluminium conductors, AWG 14–2/0 |
| Connection Pitch | 27 mm |
| Accessory Slots | One auxiliary switch slot, one undervoltage or shunt release slot, and one alarm switch slot |
| Height | 137 mm |
| Width | 81 mm |
| Depth | 89 mm |
| Mounting Height | 114 mm |
| Net Weight | 1.315 kg |
| Colour | Grey, RAL 7016 |
| Front Cover Protection | IP40, IEC 60529 |
| Impact Protection | IK07, IEC 62262 |
| Pollution Degree | 3, IEC 60947-1 |
| Operating Temperature | −25°C to +70°C |
| Storage Temperature | −50°C to +85°C |
| Operating Altitude | Below 2,000 m without derating; up to 5,000 m with derating |
| Mechanical Durability | 20,000 operating cycles |
| Electrical Durability | 10,000 operating cycles at 440 V and rated current |
| Applicable Standards | UL 489; CSA C22.2 No. 5; NEMA AB1; EN/IEC 60947-2; EN/IEC 60947-5-1; NMX J-266; GB 14048.2 |
The BGA36080 is a PowerPact B thermal-magnetic circuit breaker designed for electrical distribution. It has three poles, an 80 A rated current and an I-Line mounting arrangement.
The thermal element provides protection against sustained overloads, while the magnetic element responds to short-circuit currents. This combination provides two forms of overcurrent protection within the same breaker.
The breaker has a rated current of 80 A and an 80% continuous current rating. These are separate specifications and should both be considered when selecting the breaker for a distribution circuit.
The BGA36080 is specified for AC systems operating at 50 or 60 Hz, with breaking-capacity ratings covering 208Y/120 V, 240 V, 480Y/277 V, 480 V and 600Y/347 V. The 600Y/347 V rating should not be interpreted as a general 600 V rating for every network configuration.
Under UL 489, the breaking capacity is 65 kA at 208Y/120 V and 240 V AC, 35 kA at 480Y/277 V and 480 V AC, and 18 kA at 600Y/347 V AC. Selection must account for the system voltage and the available fault current at the installation point.
It uses I-Line mounting, with an I-Line connection on the line side and lug connections on the load side. Its phase connection is ABC. Compatibility with the intended I-Line distribution equipment should be confirmed before selection.
The breaker measures 137 mm high, 81 mm wide and 89 mm deep, with a mounting height of 114 mm. Its net weight is approximately 1.315 kg. Space for conductors and any fitted accessories should also be considered.
The load terminals accommodate copper or aluminium conductors from AWG 14 to AWG 2/0. Terminal acceptance does not establish the correct conductor size for an 80 A circuit; conductor selection must also account for the load and applicable installation requirements.
The breaker provides one slot for an OF auxiliary switch, one for an MN undervoltage release or MX shunt release, and one for an SD alarm switch. These provisions do not mean the accessories are fitted or included with every unit.
The stated operating temperature range is -25°C to +70°C, and the storage temperature range is -50°C to +85°C. The datasheet specifies operation below 2,000 m without altitude derating and up to 5,000 m with derating.
The front cover is rated IP40 under IEC 60529 and IK07 under IEC 62262. IP40 does not provide protection against water, so the installation enclosure must be selected to suit the surrounding conditions.
The BGA36080 is identified as suitable for isolation under IEC 60947-2. It has a toggle operating mechanism and is classified as utilisation category A.
This content has been produced using multiple sources. EU Automation takes no responsibility for the accuracy of this information. Always consult the original equipment manufacturer for the most up to date instructions and information.
All parts new or reconditioned are covered by EU Automation 12 month warranty
No hassle returns policy
Dedicated customer support team
We understand that credit is a necessary part of business and offer credit agreements on request, subject to status.
Payment optionsWe accept Bank transfers and the following methods of payment:
All transactions are handled securely by HSBC and HSBC Merchant Services. For more information, please visit our dedicated payments page.
Global supplier of quality automation and control components
Dispose of your old unit by exchanging it for a working part.
A comprehensive repair service for faulty equipment.
Discover how we do our part to keep your production lines moving.