What is the voltage requirement for the UE401-A0010 safety relay?
The UE401-A0010 safety relay requires a supply voltage of 24 V DC, with an acceptable range from 19.2 V DC to 28.8 V DC.
Can this safety relay be mounted on a DIN rail?
Yes, the UE401-A0010 is designed for snap-on mounting onto a 35 mm DIN rail in accordance with EN 60715.
What type of outputs does the UE401-A0010 have?
The UE401-A0010 features two PNP semiconductor outputs that are short-circuit proof and monitored for cross-circuiting.
What is the response time of this safety relay?
The UE401-A0010 has a response time of less than or equal to 30 ms.
What is the maximum cable length allowed for connecting sensors to the UE401-A0010?
The maximum cable length for sensor connection to the UE401-A0010 is 100 meters.
What is the safety integrity level of the UE401-A0010?
The UE401-A0010 is rated at Safety Integrity Level SIL3 according to IEC 61508.
What is the protection class of the UE401-A0010?
The UE401-A0010 is classified as protection class III according to IEC 61140.
What are the dimensions of the UE401-A0010?
The dimensions of the UE401-A0010 are 22.6 mm in width, 99 mm in height, and 113.5 mm in depth.
What environmental conditions can the UE401-A0010 operate under?
The UE401-A0010 can operate in temperatures ranging from -20 °C to +55 °C and can be stored in temperatures from -25 °C to +75 °C. It has an IP20 rating and should not be exposed to condensing moisture.
How many sensor pairs can be connected to the UE401-A0010?
You can connect 1 to 8 sensor pairs (transmitter and receiver) to the UE401-A0010.