steve
Got hold of Sime for a Carrier card for…
Got hold of Sime for a Carrier card for a chiller. Machine down in a factory. Received the new card in express time machine and plant now up and running fantastic service form Sime
2 months ago
Full 12-month warranty
Available for dispatch immediately
We deliver worldwide
1. Email confirmation
You will get an email confirming that we have received your enquiry.
2. Dedicated Account Manager
One of our team will be in touch to confirm your part(s) specification and condition.
3. Your quote
You will receive a comprehensive quote tailored to your specific needs.
All orders are subject to product availability. See our T&Cs.
Ask our team
1. Email confirmation
You will get an email confirming that we have received your enquiry.
2. Dedicated Account Manager
One of our team will be in touch to confirm your part(s) specification and condition.
3. Your quote
You will receive a comprehensive quote tailored to your specific needs.
| Specification | Description |
|---|---|
| Manufacturer | Murr Elektronik |
| Part Number | 6652507 |
| Product Name / Series | MIRO TR 90–250 VAC FK Opto-Coupler Module |
| Part Description | Slim DIN-rail opto-coupler interface module designed to accept a wide-range AC control signal and provide an electrically isolated transistor switching output for DC loads up to 0.5 A, with status indication. |
| Module Function | Opto-coupler / interface relay alternative (transistor output) |
| Input Type | AC control input |
| Nominal Input | 230 V AC |
| Input Voltage Range (ON) | 90…250 V AC |
| Input Voltage Range (OFF) | 0…40 V AC |
| Control Current (Input) | 7 mA |
| Output Type | Transistor output |
| Output Switching Voltage | 5…48 V DC |
| Output Switching Current (per output) | 0.1 mA…0.5 A |
| Leakage Current (output open) | Max. 0.3 mA |
| Saturation Voltage (across output) | Max. 1.2 V DC |
| Switching Time (ON / OFF) | 55 ms / 15 ms |
| Switching Frequency (max.) | 500 Hz (resistive) / 30 Hz (inductive) |
| Status Indication | Yellow LED |
| Isolation Test Voltage | 3.75 kV |
| Mounting Method | DIN-rail mountable (EN 60715) |
| Connection Type | Spring clamp terminals |
| Operating Temperature Range | -20…+60 °C |
| Housing Material / Colour | Black flame-retardant plastic |
| Dimensions (H × W × D) | 78 × 6.2 × 70 mm |
| Country of Origin | CZ |
| EAN | 4048879021821 |
| eClass | 27371601 |
| Customs Tariff Number | 85414900 |
It provides galvanic isolation between a mains AC control signal on the input side and a low-voltage DC switching output on the load side, using an optocoupler and a transistor output stage. This helps separate high-voltage control circuits from 5–48 VDC control loads.
The input switches ON in the range 90…250 VAC. Below this it will not reliably switch on.
The input is specified OFF at 0…40 VAC, which helps avoid unintended switching at low AC voltages.
The control current is specified as 7 mA on the input side.
It provides a transistor DC output designed for switching DC loads within a 5…48 VDC switching voltage range.
The switching current per output is specified from 0.1 mA up to 0.5 A maximum.
With the output open (off state), leakage current is specified at a maximum of 0.3 mA. For very small loads, this leakage may be noticeable, so verify the load’s off-state requirements.
The saturation voltage across the output is specified as a maximum of 1.2 VDC, which can be used to estimate the voltage available to the load at the chosen current.
Typical switching times are 55 ms ON and 15 ms OFF, making it suitable for many control and signalling tasks rather than high-speed switching.
Maximum switching frequency is specified as up to 500 Hz for resistive loads and up to 30 Hz for inductive loads.
Yes. The module’s test isolation voltage is specified as 3.75 kV, providing strong separation between the AC input and DC output circuits.
It is DIN-rail mountable in accordance with EN 60715, allowing quick installation alongside other control components.
It uses spring clamp terminals, which are designed for fast, reliable connections without screw tightening.
Yes. A yellow LED display indicates the switching status.
The specified operating temperature range is -20…+60 °C.
Its dimensions are 78 × 6.2 × 70 mm (H × W × D). The 6.2 mm width makes it suitable for high-density cabinet layouts.
Yes, that is a common use case: a mains AC input (within 90…250 VAC) can switch a DC load powered at 24 VDC, provided the load current remains within the 0.5 A maximum and the application tolerates the specified switching times and leakage current.
It is supplied in a black, flame-retardant plastic housing.
It is specified as a single optocoupler interface module with one input and one transistor output (commonly referenced by the article 6652507 in documentation).
This content has been produced using multiple sources. EU Automation takes no responsibility for the accuracy of this information. Always consult the original equipment manufacturer for the most up to date instructions and information.
All parts new or reconditioned are covered by EU Automation 12 month warranty
No hassle returns policy
Dedicated customer support team
We understand that credit is a necessary part of business and offer credit agreements on request, subject to status.
Payment optionsWe accept Bank transfers and the following methods of payment:
All transactions are handled securely by HSBC and HSBC Merchant Services. For more information, please visit our dedicated payments page.
Global supplier of quality automation and control components
Dispose of your old unit by exchanging it for a working part.
A comprehensive repair service for faulty equipment.
Discover how we do our part to keep your production lines moving.