What is the voltage requirement for this safety relay?
The safety relay requires a supply voltage of 24 VDC.
Can this relay be used for monitoring emergency stop functions?
Yes, it is designed for monitoring E-STOP, safety gates, and other safety functions.
What are the contact configurations of this relay?
The relay features 3 normally open (N/O) contacts and 1 normally closed (N/C) contact.
What type of start does this relay support?
It supports automatic, manual, and monitored start options.
What is the maximum current for AC1 safety contacts?
The maximum current for AC1 safety contacts is 6 A.
What is the width of the relay?
The width of the relay is 22.5 mm, making it compact and suitable for tight spaces.
What type of terminals does this relay have?
It comes with plug-in screw terminals for secure and reliable connections.
Is the relay suitable for use in various mounting positions?
Yes, the relay can be mounted in any position, providing flexibility in installation.
What is the operating temperature range for this relay?
The operating temperature range is from -10 to 55 degrees Celsius.
Does the relay comply with environmental standards?
The relay is REACh compliant, containing minimal substances of very high concern (SVHC).