What does an electronic overcurrent relay do in a motor starter?
It monitors motor current and trips when overload conditions occur, helping to protect the motor against overheating. This unit also detects phase failure and can respond to locked-rotor or mechanical jamming conditions when current rises above a multiple of the set value.
What supply voltage does it require?
It is designed for a 200 to 240 V AC supply, 50/60 Hz.
What current range can be set for thermal protection?
The thermal protection adjustment range is 20 to 38 A, allowing you to set protection according to the motor’s full-load current.
How quickly does it detect phase failure?
Phase failure sensitivity is specified as less than 3 seconds.
How does it respond to locked-rotor or mechanical jamming conditions?
It is designed to detect locked rotor/mechanical jamming when current exceeds 3 times the configured current setting (I > 3 × Isetting) and then trip accordingly.
What mounting options are available?
It can be mounted directly on compatible contactors (LC1D25 to LC1D38) or mounted on a DIN rail.
What type of output contact does it provide?
It provides one changeover contact (1 C/O) for control/indication circuits.
What reset options are available after a trip?
Reset can be automatic (fixed 120 seconds), manual, or electrical by interrupting the power supply for a minimum of 0.1 seconds.
What time-delay adjustments are available?
Time adjustment is provided via front controls with ranges including 0.2 to 10 seconds (O-time knob), 0.3 to 10 seconds (O-time knob), and 0.5 to 30 seconds (D-time knob), depending on the selected function.
How is status indicated on the unit?
It includes two LEDs for local signalling and status indication.
What are the key electrical ratings for insulation and impulse withstand?
Rated impulse withstand voltage (Uimp) is 6 kV. Rated insulation voltage (Ui) is up to 690 V (IEC) for the power circuit and 600 V (UL/CSA) for the power circuit, with rated operational voltage up to 690 V AC 50/60 Hz (IEC) for the power circuit.
What are the operating environment limits and enclosure rating?
It is rated IP20 and is specified for operation from -25 to +60 °C, with storage from -30 to +80 °C, and operation up to 2000 m altitude.
What cable sizes and tightening torques should be used on the terminals?
Control circuit terminals accept flexible conductors typically from 1 to 25 mm² (with or without cable end, depending on termination method). Power circuit terminals accept flexible conductors typically from 1 to 6 mm² (without cable end) or 2.5 to 10 mm² (with cable end). Tightening torque is 0.6 to 1.2 N·m for the control circuit on lug-clamp terminals and 2 N·m for the power circuit on cable connections.
What are the approximate dimensions and weight for panel layout planning?
Overall dimensions are approximately 67.5 mm (H) × 45 mm (W) × 67.5 mm (D), with a net weight of about 0.172 kg.
Which product standards and approvals are referenced for this device?
It is specified against IEC 60947 and IEC 60255-6, and product certifications include UL, CSA and GOST (as referenced in the product data).