What is this terminal block used for?
The SLKK 5 is a double-level terminal block designed for compact wiring of three-wire cables in control panels. Typical applications include connections for external actuating drives, solenoid valves and limit switches.
How are the connection levels arranged?
The terminal block has two laterally offset feed-through levels and a protective conductor connection to the DIN rail. This arrangement allows circuit wiring and protective earthing to be accommodated within a compact assembly.
What are the nominal voltage and current ratings?
The nominal ratings are 500 V and 30 A. The specified maximum load current of 30 A applies with a 4 mm² conductor cross-section. Approval-specific ratings may differ.
Which conductor sizes can be connected?
The screw terminals accept solid and flexible conductors from 0.2 to 4 mm². Flexible conductors fitted with ferrules without plastic sleeves are accepted from 0.25 to 4 mm², while those with plastic-sleeved ferrules are accepted from 0.25 to 2.5 mm².
Which DIN rail profiles are compatible?
The terminal block mounts on NS 35/7.5 and NS 35/15 DIN rails. Its protective conductor connection uses the DIN rail as an earthing busbar.
What are the terminal block's dimensions?
The body is 6.2 mm wide and 66.5 mm long. The mounted height is 69.5 mm on NS 35/7.5 rail or 77 mm on NS 35/15 rail. The specified end cover adds 2.5 mm to the assembly width.
What wire preparation and tightening torque are specified?
The specified conductor stripping length is 8 mm. The M3 terminal screws require a tightening torque between 0.6 and 0.8 Nm.
Can two conductors share one terminal connection?
Yes. Two solid or stranded conductors of the same cross-section can be connected within the specified range of 0.2 to 1.5 mm² per conductor. For two flexible conductors using a plastic-sleeved TWIN ferrule, the permitted range is 0.5 to 1.5 mm² per conductor.
Can the upper level be bridged to form a common connection?
Yes. The specified FBI 10-6 fixed bridge can connect the upper-level return lines for external loads and LEDs to a common busbar.
Which accessories are listed for building a terminal assembly?
Listed accessories include the D-UKK 3/5 end cover, E/UK and E/UK 1 end clamps, separating plates, bridging components and terminal markers. These allow the assembly to be secured, separated, interconnected and labelled to suit the wiring layout.
What material is used for the insulating housing?
The grey housing is made from polyamide, designated PA. Its insulating material has a UL 94 V0 flammability classification.
What operating temperature range is specified?
The specified operating temperature range is -60 °C to +105 °C, with a maximum short-term operating temperature of +125 °C. Assembly and actuation have a separate specified ambient temperature range of -5 °C to +70 °C.