steve
Got hold of Sime for a Carrier card for…
Got hold of Sime for a Carrier card for a chiller. Machine down in a factory. Received the new card in express time machine and plant now up and running fantastic service form Sime
1 month ago
Full 12-month warranty
Available for dispatch immediately
We deliver worldwide
1. Email confirmation
You will get an email confirming that we have received your enquiry.
2. Dedicated Account Manager
One of our team will be in touch to confirm your part(s) specification and condition.
3. Your quote
You will receive a comprehensive quote tailored to your specific needs.
All orders are subject to product availability. See our T&Cs.
Ask our team
1. Email confirmation
You will get an email confirming that we have received your enquiry.
2. Dedicated Account Manager
One of our team will be in touch to confirm your part(s) specification and condition.
3. Your quote
You will receive a comprehensive quote tailored to your specific needs.
| Specification | Description |
|---|---|
| Part Number | C25H32M220 |
| Manufacturer | Schneider Electric |
| Range | ComPacT (new generation) |
| Product Name | ComPacT NSX (new generation) |
| Device Short Name | NSX250H |
| Product Type | Moulded-case circuit breaker (MCCB) |
| Part Description | Three-pole ComPacT NSX250H circuit breaker with MicroLogic 2.2 M electronic trip unit, designed for dependable motor circuit protection in AC power systems up to 690 V. |
| Device Application | Motor protection |
| Poles | 3P |
| Protected Poles Description | 3D |
| Rated Current (In) | 220 A (at 65 °C) |
| Rated Operational Voltage (Ue) | Up to 690 V AC, 50/60 Hz |
| Network Type | AC |
| Network Frequency | 50/60 Hz |
| Suitability for Isolation | Yes (EN/IEC 60947-2) |
| Utilisation Category | Category A |
| Performance Level | H (70 kA at 415 V AC) |
| Trip Unit Name | MicroLogic 2.2 M |
| Trip Unit Technology | Electronic |
| Trip Unit Protection Functions | LSoI (Long-time, Short-time with fixed delay, Instantaneous) |
| Trip Unit Rating | 220 A (at 65 °C) |
| Ultimate Short-Circuit Breaking Capacity (Icu) | 100 kA at 220/240 V AC; 70 kA at 380/415 V AC; 65 kA at 440 V AC; 50 kA at 500 V AC; 35 kA at 525 V AC; 10 kA at 660/690 V AC (IEC 60947-2); 15 kA at 600 V AC (UL 508) |
| Service Short-Circuit Breaking Capacity (Ics) | 100 kA at 220/240 V AC; 70 kA at 380/415 V AC; 65 kA at 440 V AC; 50 kA at 500 V AC; 35 kA at 525 V AC; 10 kA at 660/690 V AC (IEC 60947-2) |
| Rated Insulation Voltage (Ui) | 800 V AC (50/60 Hz) |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Control Type | Toggle |
| Mounting Mode | Fixed |
| Mounting Support | Backplate |
| Mounting Position | Horizontal or vertical (flat on the back) |
| Connection Orientation | Upside connection: front; downside connection: front |
| Connection Pitch | 35 mm |
| Long-Time Pick-Up (Ir) | Adjustable, 9 settings; 100 to 220 A |
| Long-Time Delay (tr) | Fixed (trip class dependent) |
| Motor Tripping Class | Selectable: 5 / 10 / 20 |
| Thermal Memory | 20 minutes before and after tripping |
| Short-Time Pick-Up (Isd) | Adjustable, 9 settings; 5 to 13 × Ir |
| Short-Time Delay (tsd) | Fixed |
| Instantaneous Pick-Up (Ii) | Fixed; 3300 A |
| Complementary Motor Protection | Phase unbalance |
| Earth-Leakage Protection | None |
| Zone Selective Interlocking (ZSI) | None |
| Slots for Electrical Auxiliaries | 5 slots |
| Local Signalling | Flashing green LED (ready to operate); red LED (temperature over set point at 95% Ith) |
| Power Dissipation per Pole | 17.6 W |
| Mechanical Durability | 20,000 cycles |
| Electrical Durability | 20,000 cycles at 440 V (In/2); 10,000 cycles at 440 V (In); 10,000 cycles at 690 V (In/2); 5,000 cycles at 690 V (In) |
| Degree of Protection | IP40 |
| Impact Resistance | IK07 |
| Standards | EN/IEC 60947-2 |
| Overvoltage Category | Class II |
| Electrical Shock Protection Class | Class II |
| Pollution Degree | 3 (IEC 60664-1) |
| Operating Ambient Temperature | -25 to +70 °C |
| Storage Ambient Temperature | -50 to +85 °C |
| Relative Humidity | 0 to 95% |
| Operating Altitude | 0 to 2000 m (no derating); 2000 to 5000 m (with derating) |
| Dimensions (W × H × D) | 105 × 161 × 86 mm |
| Product Weight | 2.4 kg |
It is a fixed-mount moulded case circuit breaker designed for motor protection, combining overload and short-circuit protection functions via an electronic trip unit (MicroLogic 2.2 M).
It is a 3-pole device (3P) with 3 protected poles (3D), meaning all three phases are protected and monitored by the trip unit.
The rated current is 220 A at 65 °C. The long-time (thermal) pick-up Ir is adjustable from 100 to 220 A in 9 settings, allowing you to match the motor/load current.
It is intended for AC networks at 50/60 Hz with a rated operational voltage up to 690 V AC.
It is an H performance level unit (70 kA at 415 V AC). Typical ultimate short-circuit breaking capacities (Icu) include 70 kA at 380/415 V AC, 65 kA at 440 V AC, and 10 kA at 660/690 V AC (IEC 60947-2).
The trip unit provides L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous short-circuit) protection functions.
Yes. Long-time pick-up Ir is adjustable (100–220 A). Short-time pick-up Isd is adjustable from 5 to 13 × Ir (9 settings). The instantaneous pick-up Ii is fixed at 3300 A. Time delays for long-time and short-time are fixed by design.
It supports motor tripping classes 5, 10, and 20 with defined long-time delay characteristics, helping accommodate different starting profiles while maintaining protection coordination.
No. Earth-leakage protection is not included on this version, so a separate solution is required if residual current protection is needed.
Yes. It is suitable for isolation in accordance with EN/IEC 60947-2.
It is a fixed device intended for backplate mounting. It can be mounted horizontally or vertically (flat on the back). Connections are front-facing for both top and bottom, with a 35 mm connection pitch.
Overall dimensions are approximately 105 mm (W) × 161 mm (H) × 86 mm (D), with a net weight around 2.4 kg.
It includes local LED indication: a flashing green LED for ready-to-operate, and a red LED at 95% Ith to indicate temperature above the set point.
Yes. The device provides 5 slots for electrical auxiliaries, enabling configuration with compatible auxiliary functions where required.
Typical ratings include IP40 and IK07. Operating ambient temperature is -25 to 70 °C, storage is -50 to 85 °C, and relative humidity is 0–95%. Operating altitude is 0–2000 m without derating and 2000–5000 m with derating.
Power dissipation per pole is specified around 13.55 W (some documentation variants state 17.6 W per pole), which should be considered when assessing enclosure thermal performance.
Mechanical durability is specified at 20,000 cycles. Electrical durability is specified up to 20,000 cycles at 440 V (In/2), 10,000 cycles at 440 V (In), 10,000 cycles at 690 V (In/2), and 5,000 cycles at 690 V (In).
It is specified to EN/IEC 60947-2. The insulation ratings include Ui 800 V AC and impulse withstand Uimp 8 kV.
Yes. Complementary motor protection includes phase unbalance functionality as part of the protection feature set.
This content has been produced using multiple sources. EU Automation takes no responsibility for the accuracy of this information. Always consult the original equipment manufacturer for the most up to date instructions and information.
All parts new or reconditioned are covered by EU Automation 12 month warranty
No hassle returns policy
Dedicated customer support team
We understand that credit is a necessary part of business and offer credit agreements on request, subject to status.
Payment optionsWe accept Bank transfers and the following methods of payment:
All transactions are handled securely by HSBC and HSBC Merchant Services. For more information, please visit our dedicated payments page.
Global supplier of quality automation and control components
Dispose of your old unit by exchanging it for a working part.
A comprehensive repair service for faulty equipment.
Discover how we do our part to keep your production lines moving.