steve
Got hold of Sime for a Carrier card for…
Got hold of Sime for a Carrier card for a chiller. Machine down in a factory. Received the new card in express time machine and plant now up and running fantastic service form Sime
3 weeks ago
Full 12-month warranty
Available for dispatch immediately
We deliver worldwide
1. Email confirmation
You will get an email confirming that we have received your enquiry.
2. Dedicated Account Manager
One of our team will be in touch to confirm your part(s) specification and condition.
3. Your quote
You will receive a comprehensive quote tailored to your specific needs.
All orders are subject to product availability. See our T&Cs.
Ask our team
1. Email confirmation
You will get an email confirming that we have received your enquiry.
2. Dedicated Account Manager
One of our team will be in touch to confirm your part(s) specification and condition.
3. Your quote
You will receive a comprehensive quote tailored to your specific needs.
| Specification | Description |
|---|---|
| Part Number | 3RM1101-3AA04 |
| Alternative Part Number | 3RM11013AA04 |
| Manufacturer | Siemens |
| Product Brand Name | SIRIUS |
| Product Category | Motor Starter |
| Product Designation | Fail-safe Direct Starter |
| Design | With electronic overload protection and safety-related disconnection |
| Trip Class | CLASS 10A |
| Equipment Variant | According to IEC 60947-4-2 3 |
| Intrinsic Device Protection | Yes |
| Suitability for Operation | Device connector 3ZY12 |
| Power Loss | [W] for rated value of the current at AC in hot operating state per pole 0.01 W |
| Insulation Voltage Rated Value | 500 V |
| Overvoltage Category | III |
| Surge Voltage Resistance Rated Value | 6 kV |
| Maximum Permissible Voltage | For safe isolation between main and auxiliary circuit 500 V; between control and auxiliary circuit 250 V |
| Shock Resistance | 6g / 11 ms |
| Vibration Resistance | 1 ... 6 Hz, 15 mm; 20 m/s², 500 Hz |
| Operating Frequency Maximum | 1 1/s |
| Mechanical Service Life | (Switching cycles) typical 15 000 000 |
| Reference Code | According to IEC 81346-2 Q |
| Direct Start | Yes |
| Reverse Starting | No |
| Short Circuit Protection | No |
| EMC Emitted Interference | According to IEC 60947-1 class A |
| EMC Immunity | According to IEC 60947-1 Class A |
| Safety Device Type | According to IEC 61508-2 Type B |
| Safety Integrity Level (SIL) | According to IEC 61508 3 |
| Performance Level (PL) | According to EN ISO 13849-1 e |
| Category | According to EN ISO 13849-1 4 |
| Stop Category | According to DIN EN 60204-1 0 |
| Safe Failure Fraction (SFF) | 99.4 % |
| Average Diagnostic Coverage Level | (DCavg) 99 % |
| Diagnostics Test Interval | By internal test function maximum 600 s |
| Function Test Interval Maximum | 1 y |
| Failure Rate [FIT] | At rate of recognizable hazardous failures (λdd) 1 400 FIT |
| PFHD | With high demand rate according to EN 62061 0.00000002 1/h |
| PFDavg | With low demand rate according to IEC 61508 0.000018 |
| MTTFd | 75 y |
| Hardware Fault Tolerance | According to IEC 61508 1 |
| T1 Value | For proof test interval or service life according to IEC 61508 20 y |
| Safe State | Load circuit open |
| Protection Class IP | On the front according to IEC 60529 IP20 |
| Touch Protection | On the front according to IEC 60529 finger-safe |
| Main Circuit Number of Poles | For main current circuit 3 |
| Adjustable Current Response Value | Current of the current-dependent overload release 0.1 ... 0.5 A |
| Minimum Load | [%] 20 % |
| Type of the Motor Protection | Solid-state |
| Operating Voltage | Rated value 48 ... 500 V |
| Operating Frequency | 1 rated value 50 Hz, 2 rated value 60 Hz |
| Operational Current | At AC at 400 V rated value 0.5 A |
| Operating Power | For 3-phase motors at 400 V at 50 Hz 0 ... 0.12 kW |
| Inputs/Outputs | Input voltage at digital input at DC rated value 24 V |
| Number of CO Contacts | For auxiliary contacts 1 |
The motor starter has a trip class of CLASS 10A, which indicates the time it takes for the device to respond to an overload condition.
Yes, this motor starter is suitable for operation with a device connector 3ZY12.
The insulation voltage rated value for this motor starter is 500 V.
The motor starter offers electronic overload protection and safety-related disconnection, ensuring both device and circuit safety.
The operating frequency range for this motor starter is 50 Hz to 60 Hz, with a relative symmetrical tolerance of 10%.
The ambient operating temperature limits for this motor starter are between -25°C and +60°C during operation.
The typical mechanical service life of this motor starter is 15 million switching cycles.
The maximum operating voltage for this motor starter is 500 V.
The CLASS 10A trip class signifies that the motor starter will trip in 10 seconds or less at 600% of the rated current, providing quick protection against overloads.
The motor starter includes a feature for power supply reverse polarity protection, preventing damage from incorrect electrical connection.
This content has been produced using multiple sources. EU Automation takes no responsibility for the accuracy of this information. Always consult the original equipment manufacturer for the most up to date instructions and information.
All parts new or reconditioned are covered by EU Automation 12 month warranty
No hassle returns policy
Dedicated customer support team
We understand that credit is a necessary part of business and offer credit agreements on request, subject to status.
Payment optionsWe accept Bank transfers and the following methods of payment:
All transactions are handled securely by HSBC and HSBC Merchant Services. For more information, please visit our dedicated payments page.
Global supplier of quality automation and control components
Dispose of your old unit by exchanging it for a working part.
A comprehensive repair service for faulty equipment.
Discover how we do our part to keep your production lines moving.