What type of selector switch is this?
The XB4BD25EX is a complete Harmony XB4 rotary selector switch with a black standard handle and a chromium-plated metal bezel. It provides two maintained positions for selecting between control circuit states.
Does the handle stay in position when released?
Yes. The switch has a stay-put mechanism, so the handle remains in the selected position until it is manually turned. The two positions are separated by 90°.
What contact configuration does the switch have?
It has one normally open contact and one normally closed contact, expressed as 1 NO + 1 NC. The contacts use a slow-break operating mechanism.
What panel cut-out is required?
The switch belongs to the nominal 22 mm mounting range. The recommended finished panel hole diameter is 22.5 mm, with a specified permitted diameter of 22.3 mm to 22.7 mm.
What panel thickness and mounting clearance are needed?
The mounting arrangement accommodates panel thicknesses from 1 to 6 mm. The specified embedding depth is 43 mm, and the minimum fixing centres are 30 × 40 mm.
What are the electrical switching ratings?
The rated operational currents include 6 A at 120 V AC, 3 A at 240 V AC and 1.2 A at 600 V AC under AC-15 duty. DC-13 ratings include 0.55 A at 125 V DC, 0.27 A at 250 V DC and 0.1 A at 600 V DC. The applicable rating depends on the circuit voltage and utilisation category.
Is the 10 A thermal rating the same as the switching rating?
No. The 10 A figure is the conventional free-air thermal current rating. It should not be treated as a universal switching capacity; the rated operational current must be checked against the voltage and utilisation category of the intended circuit.
How are the electrical connections made?
Connections are made using screw-clamp terminals. The specified terminal tightening torque is 0.8 to 1.2 N·m, and the stated clamping capacity includes up to two 1.5 mm² conductors fitted with cable ends.
What ingress protection ratings are specified?
The XB4BD25EX has a stated IP65 degree of protection, together with NEMA 4X and NEMA 13 ratings. Maintaining the specified protection depends on correct installation and the surrounding enclosure arrangement.
What ambient temperatures can the switch withstand?
The specified operating ambient temperature range is −20°C to +60°C. For storage, the stated range is −40°C to +70°C.
What mechanical and electrical endurance figures are stated?
Mechanical durability is specified as 3 million operating cycles. Electrical durability is stated as 1 million cycles under defined test conditions, including AC-15 operation at 2 A and 230 V. Electrical endurance depends on the connected load and operating conditions.
What materials are used in the switch construction?
The switch combines a chromium-plated metal bezel with a Zamak fixing collar. Its electrical contacts are made from a silver alloy containing nickel, identified as Ag/Ni.