What is the function of this auxiliary contact module?
The auxiliary contact module is designed for use with DILM40 to DILM225A contactors, providing additional switching functions. It includes interlocked opposing contacts and can be used for standard applications in industrial control panels.
How many poles does this auxiliary contact module have?
This auxiliary contact module has 2 poles, with one normally open (N/O) and one normally closed (N/C) contact.
What is the rated operational current for this module?
The rated operational current for the DILM1000-XHI11-SI is 10 A for conventional free air thermal current, and it can handle 4 A at AC-15, 230 V.
Can this module be used in different environmental conditions?
Yes, the module is climatically proofed for damp heat, both constant and cyclic, and can operate in ambient temperatures ranging from -25°C to +60°C.
What type of connection does this auxiliary contact module use?
The module uses screw terminals for its connections, accommodating solid wires from 0.75 to 2.5 mm² and stranded wires from AWG 18 to 14.
What is the degree of protection offered by this module?
The auxiliary contact module has a degree of protection rated at IP20, ensuring protection against solid objects larger than 12.5 mm and not against water.
Is this module suitable for use with safety-related control functions?
Yes, the N/C contact within the module is suitable as a mirror contact for safety-related control functions, according to IEC/EN 60947-4-1 Annex F.
What are the dimensions of the screw terminals for this module?
The screw terminals can accommodate solid wires of 1 x (0.75 - 2.5) mm² or 2 x (0.75 - 2.5) mm², and the recommended screwdriver sizes are Pozidriv size 2 or standard screwdrivers of 0.8 x 5.5 or 1 x 6 mm.
What is the maximum tightening torque for the screw terminals?
The maximum tightening torque for the screw terminals of the module is 1.2 Nm.
How does this module contribute to the design verification as per IEC/EN 61439?
The module meets the product standard's requirements for design verification, including aspects like corrosion resistance, thermal stability, and resistance to UV radiation as per IEC/EN 61439.