What is the purpose of the auxiliary contact module?
The auxiliary contact module is designed to provide additional contact interfaces for a contactor. It is used to facilitate the control and monitoring of the contactor's status within an electrical circuit.
Can this auxiliary contact module be used with any contactor?
No, the DILA-XHI22 auxiliary contact module is specifically designed to be compatible with certain DILM(C) series contactors. It should be used with the contactors it is intended for to ensure proper functioning and safety.
What are the electrical specifications of this module?
The module has a rated insulation voltage of 690V AC, a rated operational voltage of 500V AC, and a conventional free air thermal current of 16A. It also has specific AC-15 and DC-13 operational current ratings depending on the voltage level.
What type of contacts does the module have?
The module contains 4 contacts in total, with 2 normally open (NO) and 2 normally closed (NC) contacts.
How is the module mounted onto a contactor?
The module is designed for front mounting onto compatible DILM(C) series contactors. It attaches directly to the front of the contactor without the need for additional tools or complex procedures.
What is the significance of having both NO and NC contacts?
Having both normally open and normally closed contacts allows for greater flexibility in control circuit design. It enables the module to be used for various signalling purposes, such as indicating whether the contactor coil is energised or de-energised.
Is there any special certification for this auxiliary contact module?
Yes, the module complies with international standards such as IEC/EN 60947-4-1, UL 508, and CSA-C22.2 No. 14-05, and it carries the CE marking.
What is the size of the auxiliary contact module?
The dimensions of the module are 45 x 42 x 45 mm, making it compact and suitable for use in various industrial control panel configurations.
Can this module be used for safety-related control functions?
Yes, the auxiliary contact module is designed with mirror contacts for highly reliable information relating to safety-related control functions, as per the relevant standards.
How does the module contribute to the functional safety of a control system?
The module's interlocked opposing contacts ensure that the NO and NC contacts cannot be closed simultaneously, which is a critical feature for safety-related applications.