What is the power rating for this contactor?
The contactor is rated for a power of 18.5 kW, making it suitable for controlling motors within this power range.
What is the coil voltage for this contactor?
The coil voltage for this contactor is 24 V, which is the control voltage for the activation of the contactor.
Can this contactor be used in both AC and DC applications?
Yes, the contactor is designed to be used for switching both AC and DC loads, with specific ratings for each application as detailed in the datasheet.
What is the rated operational current for this contactor?
The rated operational current for the contactor at AC-3 duty is 36 A, which is the current it can handle during typical motor starting and stopping operations.
What is the degree of protection provided by this contactor?
The contactor provides a degree of protection of IP20, which means it is protected against solid objects larger than 12.5 mm but not against water.
What are the terminal capacities for this contactor?
The terminal capacities for the main cable are 1 × (0.75 – 4) mm2 solid or 2 × (0.75 – 4) mm2 flexible with ferrule, and for the control circuit cables, they are 1 × (0.75 – 4) mm2 solid or 2 × (0.75 – 2.5) mm2 flexible with ferrule.
What is the mechanical lifespan of this contactor?
The mechanical lifespan of the contactor is rated at 10 million operations, indicating its durability and reliability over numerous cycles.
What is the ambient temperature range in which this contactor can operate?
The contactor can operate in an ambient temperature range of -25°C to +50°C when open and -25°C to +40°C when enclosed.
What is the tightening torque for the terminal screws?
The tightening torque for the terminal screws is 1.2 Nm, which ensures a secure and reliable connection.
How can I determine if this contactor is suitable for my application?
To determine suitability, you should compare your application's requirements, such as voltage, current, power rating, and environmental conditions, with the specifications of the contactor provided in the datasheet.